The alarmProcedure table is used by the Operational Procedures application to associate URLs with AVEVA Enterprise SCADA alarms. The alarmProcedure table contains the following internal fields:

Internal Field Name

Data Type

Description

alarmMessageFilter

longstring

The full or partial alarm message for which the procedure applies, up to 255 characters in length.

categoryFilter

longstring

The full or partial category for which the procedure applies, up to 255 characters in length.

conditionFilter

econdition

The safety condition filter pattern.

conditionFilterEnabled

oas_boolean_t

Filter the safety Condition?

description

pntdescription

A description of this alarmProcedure point, up to 47 characters in length.

pointNameFilter

longstring

The full or partial point name for which the procedure applies, up to 255 characters in length.

ptnum

slot

The record's slot number in the database.

severityFilter

sev_enum

Procedures matching this value are included in the list of procedures shown in the easy extended Operation Station (ezXOS) for a given alarm.

severityFilterEnabled

oas_boolean_t

Should procedures matching the severityFilter value should be included in the list of procedures shown in the ezXOS for a given alarm?

tableNameFilter

longstring

The table name filter pattern.

url

longstring

The absolute or relative URL for the procedure to be opened.

Related Links