AlarmProcedure table details
- Last UpdatedApr 24, 2025
- 1 minute read
The alarmProcedure table is used by the Operational Procedures application to associate URLs with AVEVA Enterprise SCADA alarms. The alarmProcedure table contains the following internal fields:
|
Internal Field Name |
Data Type |
Description |
|---|---|---|
|
alarmMessageFilter |
longstring |
The full or partial alarm message for which the procedure applies, up to 255 characters in length. |
|
categoryFilter |
longstring |
The full or partial category for which the procedure applies, up to 255 characters in length. |
|
conditionFilter |
econdition |
The safety condition filter pattern. |
|
conditionFilterEnabled |
oas_boolean_t |
Filter the safety Condition? |
|
description |
pntdescription |
A description of this alarmProcedure point, up to 47 characters in length. |
|
pointNameFilter |
longstring |
The full or partial point name for which the procedure applies, up to 255 characters in length. |
|
ptnum |
slot |
The record's slot number in the database. |
|
severityFilter |
sev_enum |
Procedures matching this value are included in the list of procedures shown in the easy extended Operation Station (ezXOS) for a given alarm. |
|
severityFilterEnabled |
oas_boolean_t |
Should procedures matching the severityFilter value should be included in the list of procedures shown in the ezXOS for a given alarm? |
|
tableNameFilter |
longstring |
The table name filter pattern. |
|
url |
longstring |
The absolute or relative URL for the procedure to be opened. |