Connection Row Edit: Scan Edit tab
- Last UpdatedJan 17, 2026
- 7 minute read
The Scan Edit tab in the connection Row Edit dialog box is used to configure details of a connection record. The fields in this tab help determine the communication mode and time limits associated with the connections, pole-cycles and delay times.

Refer to the table below for field descriptions and instructions on how to configure the editable fields in the Scan Edit tab in the connection Row Edit dialog box.
|
Items |
Description |
|---|---|
|
Comm. Mode |
Select the communication mode used by your system. Choices are:
|
|
Notes: Communication modes are configured on a project-by-project basis. You can only select
the modes used by your system. |
|
|
No communication timeout (sec) |
Enter the value in seconds. This field is dependent on the Comm. Mode selection. If the Comm. Mode field is set to Host Poll, Remote Poll or Listen Only, the value of this field is one factor in determining the maximum time that is given to a remote to respond via the connection in question. If any polled remote using this connection fails to respond within the configured time, a No-Reply alarm is generated against the remote. Reasonable settings for this field are 30 to 60 seconds on a leased line, and 90 to 120 seconds or more on a dial-out circuit. Some remotes may take several minutes to reply to the host. For Remote Poll and Listen-only, if no data has been read on this connection for that time period, all the active remotes on the connection will be marked as NO REPLY. When Comm. Mode is set to Cry-Out, this field is used for a different purpose. In cry-out communication mode, remotes dial in (or cry-out) to the host. The fact that there are no remotes dialing in does not indicate a failure condition. To ensure that the dial-in modem on the connection is not in a confused state, which might prevent remotes from dialing in, the modem is initialized if no incoming calls are received within the time period specified in this field. The No Communication Timeout field is set to a time interval wherein the host waits for a remote to dial in before the attached modem is initialized (for example, the modem is sent a connect command sequence). The Administrator-configurable initialization command (the connect command sequence) typically forces a hangup followed by auto-answer reconfiguration. A typical setting for this field is 3600 seconds (one hour). It is not recommended to set this field to a value over 32000 seconds. |
|
Maximum time to Connect (sec) |
Enter the maximum time (in seconds) required to establish a connection. The connection is between the Omnicomm process and the terminal server's TCP/IP port. It does not include modems or remotes. If the indicated time has expired and no connection has been established, the system generates an alarm and declares the connection failed. A typical setting is 10 seconds. |
|
Reconnection- delay Time (sec) |
Enter the delay time (in seconds) before attempting the next connection. This delay only applies to temporary connections. A permanent connection should always be connected unless it has no remotes. |
|
Maximum Reconnect Tries |
Enter the number of times that Omnicomm will attempt to open the same connection before failing over to another connection. Omnicomm will try to reconnect after the Maximum time to Connect (sec) time has expired. Typical Maximum Reconnect Tries are 2 and 3. |
|
Minimum Poll- Cycle Time (sec) |
Enter the minimum time delay between the beginning of one poll cycle and the start of the next poll cycle. The system will wait if a Minimum Poll Cycle Time delay is configured and the actual Omnicomm poll cycle completes before the minimum poll cycle time expires. This time delay is specified to:
|
|
Number of Poll Retries |
Enter the number of times the system should retry obtaining data from a remote if the initial query fails. For example, if you enter 3, the system sends up to three additional queries to the remote. If the system has not received any data after the configured number of retries, it continues to poll at intervals defined in the No Response Delay field within the remote record. For more information, refer to Remote Row Edit: Scan Parameters tab. This applies to poll attempts only–not to other types of command requests. |
|
Delay Between Remotes (ms) |
Enter the delay time between polling remotes on a round-robin basis. This delay only takes effect between remote records on a single communication line and does not impact between poll cycles. Use the field as required, as some field devices require "dead" time between requests before they listen for the start of the next message. The field indicates the delay time between successive polls. This delay before the next poll:
|
|
Communication Delay Time (ms) |
Enter the delay time you want to allow for additional overhead required by the communications media (radio keying times or VSAT delays). The field specifies the maximum expected delay for communication media that have inherent delays (for example., slow remotes, slow modems, poor communications lines, or satellite transmissions). This delay:
|
|
Persistent Socket |
Select the Persistent Socket checkbox to indicate that the connection is connected and the socket is active regardless of whether this connection is the primary connection for a remote. If this checkbox is not selected, the connection's socket is closed and the connection is disconnected by Omnicomm once it becomes a non-primary connection for a given remote. Notes: For a host poll connection type, the connection is established and remains open after
the AVEVA Enterprise SCADA host sends a first poll (for example, as test poll). |