DQFlagConfiguration table details
- Last UpdatedApr 24, 2025
- 1 minute read
The DQFlagConfiguration table is used to configure the collection of the configurable data quality attributes. Each record defines a condition that leads to the activation of one data quality attribute. The DQFlagConfiguration table contains the following internal fields:
|
Internal Field Name |
Data Type |
Description |
|---|---|---|
|
name |
pntname |
The name of the condition. |
|
description |
description |
The description of the condition. |
|
position |
DQFlagConfigurablePosition |
The position of the attribute in the dqFlag field. Important: AVEVA reserves the right to use the first 32 positions, as such, these positions should not be modified in any way. Positions 33–64 are available for definition of custom data quality attributes. |
|
table |
pntname |
The table containing the field whose value can activate the attribute. It can be set to Any when the same field and position will be used to activate the data quality attribute for all tables. For example, "flag.manl". |
|
field |
fieldname |
The field to check. |
|
value |
enumeration |
The value of the field that activates the attribute. |
|
ptnum |
slot |
This field represents the slot number of the record in the database. |