AVEVA Enterprise SCADA

Configure the alarm states of multistate points as safety-related

Configure the alarm states of multistate points as safety-related

  • Last UpdatedApr 24, 2025
  • 1 minute read

Perform this procedure to configure which alarm states associated with a multistate point are the result of a safety-related condition.

Before you begin

Complete the steps in Configure a point as safety-related.

To configure the alarm states of multistate points as safety-related

  1. Navigate to the Alarming tab in the multistate Row Edit dialog box for a safety-related point.

    Embedded Image (65% Scaling) (LIVE)

  2. Select Safety Related States.

    The Alarm State Setting dialog box opens.

    The message set associated with the record determines the alarm states appearing on the Alarm State Setting dialog box.

  3. In the Condition column, select SAFETY for each alarm state associated with a safety-related condition.

  4. Select Accept.

  5. Save your changes.