Analog Row Edit: Alarming tab
- Last UpdatedApr 24, 2025
- 7 minute read
The Alarming tab in the analog Row Edit dialog box enables you to set alarm conditions for the analog record being configured.




Support is provide for a number of alarm conditions for analog and flow rate points, including the following:
-
Instrument failure checking
-
HighHigh/LowLow operating-range checking
-
Rate-of-Change (ROC) checking
-
Creep Detection or instrument-deviation checking
-
Flatline Alarming checking
Each of these alarm conditions can be configured and enabled or disabled independently. You can set the conditions in the point’s record, or in the point’s easy eXtended Operator Station (ezXOS) control panel via the Alarm Limits window in ezXOS.
When you configure or modify the alarm limits of an analog record associated with an almlimit record (identified in the Alarm Limit Set field), the system transfers settings from the following sections to the almlimit record as well as any analog, rate, or flowTotalConfig records also associated with that almlimit record:
-
Level Alarming
-
Rate of Change Alarming
-
Creep Alarming
-
Setpoint Creep Alarming
-
Flatline Alarming
-
State Alarming Inhibit (Inhibits tab)
Refer to the table below for field descriptions and instructions on how to configure the editable fields.
|
Items |
Description |
|---|---|
|
Enable Email Notification |
Select to enable the record for email alarm notification. For further information on the items in this section, refer to Email Alarm Notification. |
|
Alternate Email Subject |
Select if alarms associated with this point are OASyS SCADA-related alarms. When selected, the subject line of email messages sent to defined recipients comes from the "emailSubject" application record. If the "emailSubject" application record does not exist, the subject line defaults to SCADA Alarm. When not selected, the subject line comes from the "emailMeaSubject" application record. If the "emailMeaSubject" application record does not exist, the subject line defaults to Measurement Alarm. For further information, refer to Email Alarm Notification. |
|
Email Alert Group |
Enter or select the name of the alertGroup record containing the Controllers and/or Administrators who will receive messages about alarms associated with this point. |
|
Minimum Alarm Severity |
Do one of the following:
|
|
Return to Normal Alarms, All Off- Normal Alarms, HiHi, Hi, Lo, LoLo, User Hi, User Lo, Instrument Fail, ROC, Creep, Setpoint Creep, Flatline |
Select the types of alarms that will generate email messages. Note: If you select yes for All Off-Normal Alarms:
|
|
Paging Park Time |
Enter the amount of time (in minutes) that the Field Operator has to respond to the alarm. After the time expires, the alarm message will become visible to the Controller. |
|
Paging Retry |
Enter the number of retry, or reminder, messages that will be sent until the Field Operator acknowledges the alarm or the Paging Park Time expires. |
|
Annunciated Page |
Select the Annunciated Page field to allow both the Field Operator and Controller to acknowledge the alarm. If this field is selected, the alarm will not be parked and will be visible to the Controller immediately. |
|
Instrument Fail Check |
Select to generate an alarm when an instrument failure occurs. An alarm is only generated if the analog point is connected with a Remote Terminal Unit (RTU) capable of sensing instrument failures. |
|
Instrument Fail Deadband |
Enter the deadband value to apply to the instrument’s lower and upper raw operating limits, as configured in the Minimum (EGU) and Maximum (EGU) fields on the Input tab. This value controls the sensitivity of the High and Low alarms. For more information, refer to Deadbands. |
|
Alarm Deadband |
Enter the deadband value for the analog point. This value controls the sensitivity of the High and Low alarms. For more information, refer to Deadbands. |
|
HiHi/LowLow Alarm Check |
Select to edit the HighHigh and LowLow alarm limits. Refer to Alarm Limits for more information. |
|
Hi/Low Alarm Check |
Select to edit the High and Low alarm limits. Refer to Alarm Limits for more information. |
|
HiHi Alarm Limit |
Enter the HighHigh alarm limitfor the analog point. |
|
Hi Alarm Limit |
Enter the High alarm limit for the analog point. |
|
Lo Alarm Limit |
Enter the Low alarm limit for the analog point. |
|
LoLo Alarm Limit |
Enter the LowLow alarm limit for the analog point. |
|
Enable ROC Alarm |
Select to enable the Rate of Change (ROC) alarm. If the ROC exceeds the ROC limit, an alarm is generated. Refer to Rate of Change Checks for more information. |
|
ROC Type |
Select the type of ROC alarming to use. Options:
|
|
Rate of change limit (Units/Sec) |
Enter the maximum allowable ROC (EGUs per second). |
|
Negative Rate of change limit (Units/Sec) |
Enter the maximum, negative allowable ROC (EGUs per second). |
|
Time Interval for ROC (sec) |
Enter the time interval over which the system should calculate the rate of change. |
|
Creep Detection |
Select to enable the Creep Detection alarm. If the analog value creeps out of its calibrated state by a value that exceeds the Deviation Alarm Limit, an alarm is generated. Refer to Creep Detection for more information. |
|
Deviation Alarm Limit |
Enter the maximum deviation value (EGUs) that is acceptable before calibration deteriorates. |
|
Setpoint Creep Detection |
Select to edit the Setpoint Deviation Alarm Limit field. For further information on the items in this section, refer to Setpoint Creep Alarms. |
|
Setpoint Deviation Alarm Limit |
Enter the setpoint creep limit. |
|
Flatline Alarming |
Select to enable Flatline Alarming. If the analog value does not change within the Timeout value (min), an alarm is generated. |
|
Timeout value (min) |
Enter the maximum about of time (minutes) that can pass without the analog value changing. |
|
Enable Realarm (0-255 mins) |
Enter the number of minutes after which an acknowledged alarm should re-alarm. Note: An entry of 0 disables the Re-Alarming functionality. For further information, refer to Re-Alarming. |
|
Alarming on-delay |
In this section, set the on-delay time in seconds for the desired alarm levels. When an alarm condition occurs, OASyS SCADA waits this many seconds before generating an alarm. For further information, refer to On/Off Delay enhancement. |
|
Alarming Off-delay |
In this section, set the off-delay time in seconds for the desired alarm levels. When a return to normal condition occurs, OASyS SCADA waits this many seconds before generating a return to normal alarm. For further information, refer to On/Off Delay enhancement. |
|
Maximum period of time (min) |
Enter the maximum allowable park time for alarms associated with this point. For further information, refer to Alarm Parking. |
|
Enable Alternate Alarm Limit |
Select to enable alternative alarm limits and edit the Alarm Limit Set field. For further information on the items in this section, refer to Alternate Alarm Limits. |
|
Alarm Limit Set |
Select (...) and select the desired alarmlimitset record from the Alarmlimitset Select dialog box. |
|
Enable Critical Alarming |
Select to enable critical alarming on the analog point. When the point enters an alarm state configured as critical, the application sends a Critical Alarm Active notification to the easy eXtended Operator Station (ezXOS). For further information, refer to Critical Alarms. |
|
Alarm Suppression |
Select to open the Alarm Suppression (Almsuppression) Table Edit dialog box, and configure almsuppression records associated with this record. |
|
Safety Related Point |
Selecting to flag the point as safety related allows you to easily filter the point in the RealTime database (RTDB) for reports and identify when a system change affects the point. For further information, refer to Safety points. |
|
Safety Related States |
Select to open the Alarm State Setting dialog box. For further information, refer to Safety points. |