AVEVA Enterprise SCADA

Hourly meter and meter configuration upload success logging

Hourly meter and meter configuration upload success logging

  • Last UpdatedApr 24, 2025
  • 1 minute read

Note: For information on overriding default configuration settings, refer to Modify configuration settings.

Follow this procedure to control the logging of the successful upload of either hourly meter or meter configuration data to the objectEvent table within Measurement's Electronic Flow Measurement (EFM) database.

To control the upload success logging of hourly meter or meter configuration data

  1. In the %DNADataRoot%\RealTime\config\Settings directory, either create or open the Realtime_libkrng.json file.

  2. In the object below, do one of the following:

    • To enable logging, change SPOOL_COMMAND_SUCCESS_TO_OBJECTEVENT from false to true.

    • To disable logging, change SPOOL_COMMAND_SUCCESS_TO_OBJECTEVENT from true to false.

      {

      "RealTime": {

      "SPOOL_COMMAND_SUCCESS_TO_OBJECTEVENT": true,

      "CHECK_METER_CALCULATION_SOURCE": "YES"

      }

      }

      Note: If this JSON file is absent from the above directory, logging is enabled by default.

  3. Save the file.

  4. Restart the RealTime service.