Internal Field Name |
Data Type |
Description |
|---|---|---|
|
alarm |
oas_boolean_t |
In alarm. |
|
alertMinAlmSev |
sev_enum_email |
Minimum alarm severity for point alarm notification. |
|
alminh |
oas_boolean_t |
Inhibit off-normal alarms. |
|
alminhconfig |
oas_boolean_t |
Config inhibit off-normal alarms. |
|
altTag |
flexTagAttr |
Alternate flextag/tag attribute. |
|
autoCmdAlmInh |
oas_boolean_t |
Inhibit alarms when commands generated by the automated process fail? |
|
autoCmdEvtInh |
oas_boolean_t |
Inhibit events when commands generated by the automated process fail? |
|
badTimestamp |
oas_boolean_t |
Timestamp from Remote Terminal Unit (RTU) is suspect. |
|
bmsg |
messageslot |
Base status message number. |
|
cevinh |
oas_boolean_t |
Inhibit return-to-normal logs. |
|
clrinh |
oas_boolean_t |
Inhibit return-to-normal alarms. |
|
clrinhconfig |
oas_boolean_t |
Config inhibit return-to-normal alarms. |
|
cmsg |
messageslot |
Current status message number. |
|
compositeDQ |
oas_boolean_t |
A combination of multiple data qualities. |
|
dataAttributes |
longstring |
Information for Control Room Management (CRM) objects data quality icons. |
|
error |
oas_boolean_t |
Configuration/input-data error. |
|
evtinh |
oas_boolean_t |
Inhibit off-normal logs. |
|
extendedDQ |
unsigned char |
Virtual field specifying the position of the extended data quality attribute with the highest precedence among the active data quality attributes for the point. |
|
fg |
pntcolor |
Text color. |
|
fgint |
color_char |
Enum constant of text color. |
|
flash |
oas_boolean_t |
Alarm flashing/unacknowledged. |
|
flashcount |
int |
The number of unacknowledged alarms. |
|
flexTag |
flexTagAttr |
Flex tag attribute. |
|
fresh |
oas_boolean_t |
This data is freshly updated. |
|
image |
displayname |
Image name corresponding to current message. |
|
inhalarmTime |
timestring |
Suspend time in dd:hh:mm for inhibited alarms. |
|
inhalarmTimeconfig |
timestring |
Configure suspend time in dd:hh:mm for inhibited alarms. |
|
inhsuspend_end |
long |
Suspend end time for inhibited alarms. |
|
inhtimeleft |
timeinhalmstr_12 |
Remaining time for inhibited alarms in dd:hh:mm:ss. |
|
inhtimeout |
timerslot |
Timer number for alarm inhibit. |
|
instrumentFail |
oas_boolean_t |
This field specifies if the point is in instrument failure. |
|
isClamped |
oas_boolean_t |
Value is clamped. |
|
isControllable |
oas_boolean_t |
Is point controllable? |
|
lastPntCnd |
oas_boolean_t |
What was the last replicated flag.fresh? |
|
manl |
oas_boolean_t |
Is point on manual over-ride? |
|
msgtxt |
msgstring |
Text field corresponding to current message. |
|
offscan |
oas_boolean_t |
Is the remote off-scan? |
|
packqual |
packqualtype |
XOS compact data quality. |
|
pntcnd_isStale1 |
oas_boolean_t |
Is point conditioned stale? |
|
pntcnd_ptStale1 |
statusslot |
The status point serving as a Sub-Remote Status Indicator stale point. |
|
pntCndActive |
oas_boolean_t |
Point conditioning active. |
|
priorityDisplay |
modelname |
The display associated with the Priority Display icon on an easy eXtended Operator Station (ezXOS) Control dialog. |
|
realarmTime |
short |
Suspend time in minutes. |
|
rtu_alrm |
oas_boolean_t |
RTU point alarm enabled (not inhibited)? |
|
rtu_cntl |
oas_boolean_t |
Is point control-inhibited in the RTU? |
|
rtu_manl |
oas_boolean_t |
Is point on manual over-ride in the RTU? |
|
rtu_proc_alarms |
oas_boolean_t |
Enables raising an alarm against the analog record if the driver is set to collect and process RTU alarms. Otherwise, the driver raises the alarm against the RTU (protocol-specific). |
|
rtu_qsd |
oas_boolean_t |
Is point questionable data in in the RTU? |
|
safety |
oas_boolean_t |
Is the point safety-related? |
|
secondpoll |
oas_boolean_t |
Is this the second or later poll for this data? |
|
severity |
sev_enum |
Severity of alarm. |
|
sevint |
sev_char |
Enum constant of alarm severity. |
|
state_inhibited |
oas_boolean_t |
States are inhibited. |
|
tag |
tagattr |
Tag attribute. |
|
testmode |
oas_boolean_t |
Suppress alarms due to testmode. |
|
up_alrm |
oas_boolean_t |
Upload alarm inhibit bit? |
|
up_cntl |
oas_boolean_t |
Upload control inhibit bit? |
|
up_manl |
oas_boolean_t |
Upload manual inhibit bit? |
|
up_qsd |
oas_boolean_t |
Enables processing of the questionable bit (QSD) on the point (protocol-specific). |
|
userDefined1 |
oas_boolean_t |
A user-defined data quality. |
|
userDefined2 |
oas_boolean_t |
A user-defined data quality. |
|
userDefined3 |
oas_boolean_t |
A user-defined data quality. |
|
userDefined4 |
oas_boolean_t |
A user-defined data quality. |
|
userDefined5 |
oas_boolean_t |
A user-defined data quality. |
|
userDefined6 |
oas_boolean_t |
A user-defined data quality. |
|
verified |
oas_boolean_t |
Point is verified. |
|
watchdogStale |
oas_boolean_t |
Point staled by Flatline Watchdog. |