AbsoluteValueScalingValidation plugin
- Last UpdatedApr 24, 2025
- 1 minute read
This plugin checks if the entered minimum and maximum values have the same sign. If the signs are different, the system generates the following error message:
When absolute value for level alarming is enabled, minimum and maximum scaling values must be equal but with opposite signs.
The following parameters must be set:
-
Name="AbsoluteValueScalingValidation".
-
Args="<name of column for scaling check>,<name of column to enable scaling check>".
For example, the engineering units (EGUs) conversion fields in the Input tab of the Analog Row Edit form—Minimum (raw) and Maximum (raw)—are set with the AbsoluteValueScalingValidation constraint.
<Group Name="Input" >
<SubGroup Name="Conversion" >
<Field Name="iengr_@rawmin">
<FieldPlugIn Name="AbsoluteValueScalingValidation" Args="iengr_@rawmax,hilow_@absolute_alarming" />
</Field>
<Field Name="iengr_@rawmax">
<FieldPlugIn Name="AbsoluteValueScalingValidation" Args="iengr_@rawmin,hilow_@absolute_alarming" />
</Field>
</SubGroup>
If the values and signs for Minimum (raw) and Maximum (raw) are different, the system generates an error.