Prevent additional communication failure alarms
- Last UpdatedApr 24, 2025
- 1 minute read
Note: For information on overriding default configuration settings, refer to Modify configuration settings.
Follow this procedure to inhibit the system from generating further communication failure alarms for a Remote Terminal Unit (RTU) in an abnormal state after the initial failure alarm.
Note: The system will continue to log events in relation to the RTU's communication status.
To prevent additional communication failure alarms
-
In the %DNADataRoot%\RealTime\config\Settings directory, either create or open the remote.CommunicationAlarm.json file.
-
In the following line, change NO to YES.
RemoteCommunicationAlarm > "ENABLE_INDEFINITE_ALARM_SUPPRESSION": "NO"
-
Save the file.
-
Restart the RealTime service.