Prevent additional communication failure alarms

  • Last UpdatedApr 24, 2025
  • 1 minute read

Note: For information on overriding default configuration settings, refer to Modify configuration settings.

Follow this procedure to inhibit the system from generating further communication failure alarms for a Remote Terminal Unit (RTU) in an abnormal state after the initial failure alarm.

Note: The system will continue to log events in relation to the RTU's communication status.

To prevent additional communication failure alarms

  1. In the %DNADataRoot%\RealTime\config\Settings directory, either create or open the remote.CommunicationAlarm.json file.

  2. In the following line, change NO to YES.

    RemoteCommunicationAlarm > "ENABLE_INDEFINITE_ALARM_SUPPRESSION": "NO"

  3. Save the file.

  4. Restart the RealTime service.