Reminder table details
- Last UpdatedApr 24, 2025
- 3 minute read
The reminder table is used to configure custom alarms and then schedule their occurrence. You can specify reminders to be one-time alarms, one-time or recurring conditional alarms, or to recur at a specific time or date and time. The reminder table contains the following internal fields:
|
Internal Field Name |
Data Type |
Description |
|---|---|---|
|
accessFlag |
displayname |
This flag is used by easy eXtended Operator Station (ezXOS) to determine whether a table is being modified through the Advanced Database Editor (ADE). If the flag is set, access to the table is denied. |
|
analogOperator |
text4 |
This field is the mathematical operator for an analog comparison. |
|
analogSlot |
analogslot |
The analog point used for a conditional reminder. |
|
analogValue |
anaDatatype |
This field is the value of the analog point configured as part of a conditional reminder. |
|
currentAnalog |
analogslot |
The current analog point used in value comparisons for Threshold Conditional reminders. |
|
dataset |
doas_dset_slot |
This field indicates the dataset to which the record is assigned. Datasets are used to associate the record with the privileges assigned for each system mode. Once a record is assigned to a dataset value, the dataset can only be changed to a value for which the system has a privilege record. |
|
DBnPnt |
DBPointType |
This field is the database and point composite for the One-Shot Alarm. |
|
description |
pntdescription |
A description of the reminder point, up to 47 characters in length. |
|
dsysControl |
unsigned char |
This field indicates if the record is controllable from a local system. |
|
enabled |
oas_boolean_t |
This field indicates whether the reminder is currently enabled. |
|
flag |
flags |
For information on the flag structure, see Flag structure details. |
|
group |
groupslot |
This field shows the group that this point is associated with for alarming. |
|
last_time |
internaltime |
Use this field to configure the date and time at which you want the system to generate the last recurring alarm. |
|
last_time_enable |
oas_boolean_t |
This field indicates that the last time execution is enabled. |
|
message |
almsumMsg |
This field is the alarm message text, up to 256 characters in length. |
|
name |
pntname |
The unique name of the record. |
|
onetime_time |
internaltime |
This field is date/time for the one-time reminder. |
|
pointOperator |
text4 |
This field is the mathematical operator for the one-shot alarm point comparison. |
|
pointPath |
path |
This field is the reference point for the one-shot alarm. |
|
pointValue |
double |
This field is the value of the one-shot alarm point. |
|
ptnum |
unsigned char |
This field displays the slot number assigned to this record in the database. |
|
rateOperator |
text4 |
This field is the mathematical operator for the rate comparison. |
|
rateSlot |
rateslot |
The status point used for a conditional reminder. |
|
rateValue |
double |
This field is the value for the rate point configured as part of a conditional reminder. |
|
recurring |
oas_boolean_t |
This field indicates if this reminder is recurring. It is only used for a conditional reminder. |
|
reminderType |
operatorReminderType |
This field shows the type of operator reminder of this record:
|
|
severity |
sev_enum |
The field specifies the severity level of the alarm. |
|
statusSlot |
statusslot |
The status point used for a conditional reminder. |
|
statusValue |
statusStates |
This field is the value for the status point configured as part of a conditional reminder. |
|
targetAnalog |
analogslot |
The target analog point used in value comparisons for Threshold Conditional reminders. |
|
threshold |
anaDatatype |
This field is the target value of threshold. |
|
thresholdBool |
text4 |
This field is used to compare the current analog with the target analog. |
|
thresholdOper |
text4 |
This field is the mathematical operation applied to threshold. |
|
timeblk |
taskTimer |
This field allows you to specify the date/time for a scheduled reminder message (alarm) on the basis of:
|
|
timeblk_week |
text4 |
This field allows you to specify the date/time for a scheduled reminder message (alarm) by indicating the week of the month (1 to 5). |
|
todelete |
oas_boolean_t |
This field indicates if the record is marked for deletion. |