The records in the collect table are used to configure the collection of data from the analog, rate, remote, and status tables. The system sends the collected data to the Historical database (HDB).

Rather than obtaining access to the collect table information directly, you can also use Microsoft SQL statements (for example, select or delete) or RealTime utilities (for example, dbget and dbput) and registered procedures.

The collect table contains the following internal fields:

Internal Field Name

Data Type

Description

accessFlag

displayname

This flag is used by easy eXtended Operator Station (ezXOS) to determine whether a table is being modified through the Advanced Database Editor (ADE). If the flag is set, access to the table is denied.

colBuffer

collect_buffer

An array that stores the actual buffer of collect data for a point.

collectPeriod

period

Sets the units to use for the time period for interval data.

collectVar

collect_type

The type of collection that occurs for this point.

currentMsg

unsigned char

The current transfer message number for replication to standby RealTime host(s).

dbpath

path

The structure that stores the data path to the point.

deadBand

double

The deadband for exception collection.

deleteRec

oas_boolean_t

Should the collect record be deleted after it is flushed to Historical?

firstSumXfr

collect_time

The last summary row that was sent to standby.

flushCollect

oas_boolean_t

Are records ready to be flushed to Historical?

flushHead

unsigned short

Index indicating where to start flushing data to Historical.

flushTail

unsigned short

Index indicating where to stop flushing data to Historical.

flushOwned

oas_boolean_t

Collect transfer to flush owned rows.

flushOwnedTm

internaltime

Time of mode switch where ownership was relinquished.

flushUnowned

oas_boolean_t

Collect transfer to flush non-owned rows.

flushUnownedTm

internaltime

Time of mode switch where ownership was asserted.

isOwned

oas_boolean_t

Local system owns this data as of the last known rows.

lastCollect

collect_time

The time of the last collection.

lastCollectMil

short

Millisecond interval of the last collection.

lastData

unsigned short

Index indicating the most recent data.

lastDQFlags

long

Data quality flags of the last point collected.

lastStatus

char

The status of the last point collected.

lastSummary

collect_time

The last hour summarized.

lastSumXfr

collect_time

Oldest summary row sent to standby.

lastSumXfrNum

unsigned short

The number of rows previously replicated to the standby RealTime host(s).

lastValue

collect_value

Last value collected.

numFlush

unsigned short

Number of unflushed items in the collect buffer.

numPeriod

short

Number of periods between interval data samples.

numSummary

unsigned short

Number of items in the summary buffer.

numTrend

unsigned short

Number of values that can be used in trending.

numXfr

unsigned short

Number of points waiting for replication to the standby RealTime host(s).

ptName

collect_name

This field shows the name of this collect point.

ptnum

unsiged char

This field represents the record’s slot number in the database.

summarize

oas_boolean_t

Should this collect point be summarized?

sumBuffer

summary_buffer

Array that stores the actual buffer of summary data.

tagID

int

Last known Historical timeline tagID.

trendHead

unsigned short

Index indicating the oldest data start.

upldDaySum

oas_boolean_t

Collect the uploaded day summary from the device?

xfrHead

unsigned short

Index indicating where to start flushing to standby.