Configure an analog point as a critical point
- Last UpdatedApr 24, 2025
- 2 minute read
Follow this procedure to configure an analog point as a critical point. When the point enters an alarm state configured as critical, the application sends a Critical Alarm Active notification to easy eXtended Operator Station (ezXOS).
To configure an analog point as a critical point
-
Navigate to the message Table Edit dialog box in the Advanced Database Editor (ADE).
-
Create a new message set.
-
Navigate to the Main tab in the message Row Edit dialog box for the state that triggers a critical alarm.

-
In the State Severity field, select critical.
-
Repeat steps 3 and 4 for all states in the message set that trigger a critical alarm.
For further information on message sets, refer to RealTime tables.
-
Navigate to the Main tab in the analog Row Edit dialog box for the point you want to configure as a critical point.
-
In the Base Message field, select the newly created message set (message record).
-
Navigate to the Alarming tab.

-
Select Enable Critical Alarming.