FcConfigTelemetered table details
- Last UpdatedApr 24, 2025
- 2 minute read
The fcConfigTelemetered table is used by the Flow Computer Management application. The records in the fcConfigTelemetered table store flow computer configuration information. This information ensures the telemetered flow computer functions as expected. The fcConfigTelemetered table contains the following internal fields:
|
Internal Field Name |
Data Type |
Description |
|---|---|---|
|
dataset |
doas_dset_slot |
This field indicates the dataset to which the record is assigned. Datasets are used to associate the record with the privileges assigned for each system mode. Once a record is assigned to a dataset value, the dataset can only be changed to a value for which the system has a privilege record. |
|
densAnalog |
analogslot |
The analog point that represents the density. |
|
densProvided |
oas_boolean_t |
Enable the collection of density information from the configured analog point? |
|
description |
description |
A description of this fcConfigTelemetered point, up to 47 characters in length. |
|
flag |
flags |
For information on the flag structure, see Flag structure details. |
|
group |
groupslot |
The group that this point is associated with for alarming. |
|
gsvRate |
rateslot |
The rate point that provides the Gross Standard Volume (GSV) of the current batch and the flow rate of the meter. |
|
lastCompletedTicket.batchIdAnalog |
analogslot |
The analog point that represents the completed ticket's Batch ID. |
|
lastCompletedTicket.cswAnalog |
analogslot |
The analog point that represents the completed ticket's Correction for Sediment and Water (CSW). |
|
lastCompletedTicket.endingGsvAnalog |
analogslot |
The analog point that represents the completed ticket’s ending GSV. |
|
lastCompletedTicket.endingIvAnalog |
analogslot |
The analog point that represents the completed ticket’s ending Indicated Volume (IV). |
|
lastCompletedTicket.ivAnalog |
analogslot |
The analog point that represents the completed ticket's IV. |
|
lastCompletedTicket.gsvAnalog |
analogslot |
The analog point that represents the completed ticket's GSV. |
|
lastCompletedTicket.mcfAnalog |
analogslot |
The analog point that represents the completed ticket's Meter Correction Factor (MCF). |
|
lastCompletedTicket.nsvAnalog |
analogslot |
The analog point that represents the completed ticket's Net Standard Volume (NSV). |
|
lastCompletedTicket.schedGSVAnalog |
analogslot |
The analog point that represents the completed ticket's Scheduled GSV. |
|
lastCompletedTicket.startingGsvAnalog |
analogslot |
The analog point that represents the completed ticket’s starting GSV. |
|
lastCompletedTicket.startingIvAnalog |
analogslot |
The analog point that represents the completed ticket’s starting IV. |
|
lastCompletedTicket.ticketNumberAnalog |
analogslot |
The analog point that represents the completed ticket number. |
|
lastCompletedTicket.wadAnalog |
analogslot |
The analog point that represents the completed ticket's Weighted Average Density (WAD). |
|
lastCompletedTicket.wafAnalog |
analogslot |
The analog point that represents the completed ticket's Weighted Average Flow (WAF). |
|
lastCompletedTicket.wapAnalog |
analogslot |
The analog point that represents the completed ticket's Weighted Average Pressure (WAP). |
|
lastCompletedTicket.watAnalog |
analogslot |
The analog point that represents the completed ticket's Weighted Average Temperature (WAT). |
|
name |
pntname |
The unique name of this fcConfigTelemetered record. The name can be up to 32 characters in length. |
|
presAnalog |
analogslot |
The analog point that provides the pressure information. |
|
presProvided |
oas_boolean_t |
Enable the collection of pressure information from the configured analog point? |
|
rtu |
remoteslot |
Name of the remote that is associated with this field device. |
|
tempAnalog |
analogslot |
The analog point that provides the temperature information. |
|
tempProvided |
oas_boolean_t |
Enable the collection of temperature information from the configured analog point? |
|
ticketIdAnalog |
analogslot |
The analog point that represents the current Ticket ID. |