Please ensure Javascript is enabled for purposes of website accessibility
Powered by Zoomin Software. For more details please contactZoomin

AVEVA Enterprise SCADA

Support output to a single register

  • Last UpdatedApr 24, 2025
  • 2 minute read

Status and multistate points can be configured to support output to a single register with a preset bit format. This allows you to configure a 16-bit register value to send to the remote.

To support output to a single register

  1. Open the Row Edit dialog box for the status or multistate record you want to configure.

  2. Select the Output tab.

    Embedded Image (65% Scaling) (LIVE)

  3. Configure the Command field to support a single register output. You can configure the setting for Command #1, Command #2, or both commands.

    1. In the Command field, select (...).

      The ogxOutputCMD dialog box appears.

    2. Select Single Reg Output, and select Accept.

    3. Save the record changes.

  4. Select Configure Bit Pattern.

    The Bit Mask Selector dialog box appears.

    Note: The Bit Mask Selector options are only available if Single Reg Output is selected for the command.

  5. Configure the 16-character bit pattern you want to send to the remote when the command is executed.

    1. Select the tab of the command (Command #1 or Command #2) for which you want to configure the single register output.

    2. Select the bit numbers you want to include in your 16-character bit pattern or enter the number in the Value field.

    3. Select OK.