Configurable alarms and events
- Last UpdatedApr 24, 2025
- 1 minute read
You can configure both the severity and the message text of configurable alarms and events using one of the following three methods:
-
Configure msginfo sets — Using this method, you can configure the severity of the alarm and change the message text associated with certain alarm conditions for a specific subset of points. You can then associate different severities and messages to different points for the same alarm condition.
-
Configure an Alarm Override — Using this method, you can only configure the severity of the alarm and associate different severities for alarm conditions based on which RealTime database (RTDB) table and/or which AVEVA Enterprise SCADAprocess raises the alarm condition.
-
Edit the RealTime_ConfigurableAlarmSeverity.json file — Using this method for the existing alarming conditions, you can switch the feature on or off.
For more information, refer to Alarms and events.