AVEVA Enterprise SCADA

Alarm Audit table

  • Last UpdatedApr 24, 2025
  • 3 minute read

The Historical Alarm Audit (almaudit) table audits alarms and their acknowledgment by Controllers and/or applications. The table is part of the Event database in the historical Microsoft SQL Server.

When AVEVA Enterprise SCADA generates an alarm, the AlarmSerialization program records the alarm in both the almaudit table and the RealTime database (RTDB) almsum table. Similarly, when a Controller acknowledges an alarm, the AlarmSerialization program writes the alarm acknowledgement to the almaudit table, in addition to updating the almsum table. Similarly, when a Controller acknowledges an alarm, the AlarmSerialization program writes the alarm acknowledgement to the almaudit table and updates the almsum table.

Auditors can use the Historical record in the almaudit table to examine the frequency and details of alarms seen by Controllers at any given time. While the almaudit table is similar to the OperActivitySummary table, the former contains only the actual alarms generated and acknowledged. Since the events and alarms may be inhibited separately for a given telemetered point or application-related alarm, in reality a Controller may only see an event for an alarm while the alarm itself is inhibited. By examining the contents of the almaudit table, an auditor can focus only on the alarms that were shown to the Controller and the actions taken to acknowledge the alarms.

Internal Field

Data Type

Description

time

GMTtime

This field indicates—in Greenwich Mean Time (GMT)—either the time of the alarm, or the time of the action taken against the alarm.

msec

int

This field indicates the millisecond section of the time.

offset

GMToffset

The difference (in minutes) between local time and Coordinated Universal Time (UTC) when the time field was populated.

type

nameType

This field indicates the type of the alarm. An alarm is one of the following types:

  • Database alarm

  • System alarm

  • Application alarm

host

nameType

This field indicates the name of the host associated with the alarm.

process

nameType

This field indicates the name of the application or process associated with the alarm.

dbName

nameType

This field indicates the name of the database associated with the alarm.

ptName

nameType

This field indicates the name of the point associated with the alarm.

description

descType

This field provides a description of the ptName.

rtuName

nameType

This field indicates the name of the Remote Terminal Unit (RTU) associated with the alarm.

groupName

nameType

This field indicates the name of the group to which the ptName belongs. Some alarms are not associated with a group (such as, for example, a service restart or mode switch).

message

msgType

This field indicates either the text used for the alarm message, or the command issued against the alarm.

fgInt

tinyint

This field indicates the foreground color used for the alarm’s message.

sevInt

tinyint

This field indicates the severity associated with the alarm.

key1

int

This field is related to Datapump support (for internal use only).

key2

int

This field is related to Datapump support (for internal use only).

spooler

tinyint

This field indicates the spooler number associated with groupName.

hasNote

boolType

This field is reserved for future enhancement.

datasetId

tagIDType

This field indicates the ID of the associated dataset.

ownSysId

tagIDType

This field indicates the system ID of the system that owns the alarm.

fldname

nameType

When used, this field indicates the name of the specific field that is in alarm.

category

nameType

This field indicates the category associated with the alarm.

areaName

nameType

This field is reserved for future enhancement.

annunciated

nameType

This field indicates whether or not the alarm was flashing to the Controller.

inalarm

nameType

This field indicates whether or not the alarm was persistent.

timestampstr

nameType

This field is a string representation of the time field.

covered

nameType

This field indicates whether the alarm was covered by Area Of Responsibility (AOR).

purgetimer

tinyint

This field indicates the purge timer value of the alarm in seconds.

stationName

nameType

This field indicates the RealTime station associated with the alarm.

paging_code

nameType

This field indicates the paging code associated with the alarm for pre-parking.

condition

nameType

This field indicates the safety condition associated with the alarm. Possible values are as follows:

  • NONE

  • SAFETY

tag

nameType

This field indicates the flag.tag field of the point in alarm.

alarmGUID

nchar(40)

The field is used to indicate a relation between different alarms. For further information, refer to the "Understanding Alarm Stories" section below.

alarmAuditType

tinyint

This field references the audit type of the alarm. For further information, refer to the "Understanding Alarm Stories" section below.