AVEVA Enterprise SCADA 2025 Patch 1 (July 2026 Revision) release notes
- Last UpdatedJul 08, 2026
- 10 minute read
Original Release Date
April 7, 2026
Revision Release Date
July 7, 2026
Revision Notice: This document was revised and re-released in July 2026 to address missing information in the "Update ezXOS elements in the data root" section.
Note: When you copy a file over from a network share or computer, you may need to unblock the file. After copying a file to its destination, right-click on the file and select Properties. In the Security section on the General tab, ensure that Unblock is selected.
The AVEVA Enterprise SCADA 2025 Patch 1 release is focused on reliability and stability. This update rolls up the hotfixes released since the AVEVA Enterprise SCADA 2025 release into a single, streamlined version for easier deployment and support.
The AVEVA Enterprise SCADA 2025 Patch 1 release notes describe the software, installation steps, and the fixed issues and changes that we have made since the AVEVA Enterprise SCADA 2025 release.
Note: As standard practice, projects and customers should make sure to install the latest patches for these product versions.
Note: This release is compatible with JSON serialization.
Prerequisite software
Before installing AVEVA Enterprise SCADA 2025 Patch 1, ensure that the following is already installed on the system:
-
AVEVA Enterprise SCADA 2025
Microsoft Installer (MSI)
-
Software Prerequisite MSI File(s)
To ensure a fully operational and supported system, the previously released product components (and all contents) for AVEVA Enterprise SCADA 2025 must be installed from the associated MSI file(s) prior to applying this patch.
Notes: The MSI version numbers should match the versions listed in the table; however, version numbers may be higher if you have hotfixes installed.
For more information on previously released patches, refer to the applicable set of release notes. If you do not have access to the release notes, contact the AVEVA Knowledge & Support Center.Product Component
(Microsoft Windows Program Name)MSI File name
MSI Version
Release Version
AVEVA Enterprise SCADA ADE Client
ADE.Client.msi
10.4.0.443
AVEVA Enterprise SCADA 2025
AVEVA Enterprise SCADA ADE Extensions
ADE.Extensions.msi
10.4.0.504
AVEVA Enterprise SCADA Historical Datapump
Historical.Datapump.msi
10.4.0.481
AVEVA Enterprise SCADA RealTime ADE
RealTime.ADE.msi
10.4.0.158
AVEVA Enterprise SCADA RealTime Displays
RealTime.ezXOS.msi
10.4.0.242
AVEVA Enterprise SCADA RealTime Service
RealTime.service.msi
10.4.0.1875
AVEVA Enterprise SCADA Applications VirtualRTU Player
Applications.VirtualRTU.Player.msi
10.4.0.309
AVEVA Enterprise SCADA Historical Base Infrastructure
Historical.Common.Base.msi
10.4.0.447
AVEVA Enterprise SCADA Infrastructure Common Tools
Infrastructure.Tools.Common.msi
10.4.0.781
AVEVA Enterprise SCADA Infrastructure Administration Tools
Infrastructure.Tools.Administrationn.msi
10.4.0.796
AVEVA Enterprise SCADA Management Of Change ServiceBase
ManagementOfChange.ServiceBase.msi
10.4.0.458
AVEVA Enterprise SCADA Management Of Change RealTime
ManagementOfChange.RealTime.msi
10.4.0.1013
AVEVA Enterprise SCADA OPC DA Server
OPC.DAServer.msi
10.4.0.828
AVEVA Enterprise SCADA SystemServices Common
SystemServices.Common.msi
10.4.0.707
AVEVA Enterprise SCADA SystemServices ISPS
SystemServices.ISPS.msi
10.4.0.640
AVEVA Enterprise SCADA SystemServices RCS
SystemServices.RCS.msi
10.4.0.643
-
Software Patch MSI File(s) Included in this Release
Product Component
(Microsoft Windows Program Name)MSI File name
MSI Version
Release Version
AVEVA Enterprise SCADA ADE Client
ADE.Client.msi
10.4.0.504
AVEVA Enterprise SCADA 2025 Patch 1
AVEVA Enterprise SCADA ADE Extensions
ADE.Extensions.msi
10.4.0.523
AVEVA Enterprise SCADA Historical Datapump
Historical.Datapump.msi
10.4.0.493
AVEVA Enterprise SCADA RealTime ADE
RealTime.ADE.msi
10.4.0.174
AVEVA Enterprise SCADA RealTime Displays
RealTime.ezXOS.msi
10.4.0.271
AVEVA Enterprise SCADA RealTime Service
RealTime.service.msi
10.4.0.1986
AVEVA Enterprise SCADA Applications VirtualRTU Player
Applications.VirtualRTU.Player.msi
10.4.0.323
AVEVA Enterprise SCADA Historical Base Infrastructure
Historical.Common.Base.msi
10.4.0.464
AVEVA Enterprise SCADA Infrastructure Common Tools
Infrastructure.Tools.Common.msi
10.4.0.825
AVEVA Enterprise SCADA Infrastructure Administration Tools
Infrastructure.Tools.Administrationn.msi
10.4.0.839
AVEVA Enterprise SCADA Management Of Change ServiceBase
ManagementOfChange.ServiceBase.msi
10.4.0.470
AVEVA Enterprise SCADA Management Of Change RealTime
ManagementOfChange.RealTime.msi
10.4.0.1025
AVEVA Enterprise SCADA OPC DA Server
OPC.DAServer.msi
10.4.0.841
AVEVA Enterprise SCADA SystemServices Common
SystemServices.Common.msi
10.4.0.722
AVEVA Enterprise SCADA SystemServices ISPS
SystemServices.ISPS.msi
10.4.0.655
AVEVA Enterprise SCADA SystemServices RCS
SystemServices.RCS.msi
10.4.0.664
Pre-installation configuration
There are no pre-installation requirements for this release.
Installation
To install AVEVA Enterprise SCADA 2025 Patch 1
-
Sign in to the computer as a member of DNA Installers.
-
Shut down all AVEVA Enterprise SCADA services.
-
Copy the 2025 Patch 1 MSI files to an accessible location on any computer running the MSI files listed under Software Patch MSI File(s) in Prerequisite software.
-
Run the individual 2025 Patch 1 MSI files.
-
Apply the post-installation configuration procedures.
Post-installation configuration
Apply configuration changes to the affected products.
Advanced Database Editor (ADE)
-
Sign in as a member of DNA Installers.
-
Start an elevated PowerShell session.
-
Run the following commands:
set-silo ADE
start-configtool.ps1
Config Tool opens.
-
Select Initial.
-
In the Features section, only select the following:
-
ADE
-
ADE Schema
-
-
Select Run.
Common
-
Sign in as a member of DNA Installers.
-
Start an elevated PowerShell session.
-
Run the following commands:
set-silo Common
start-configtool.ps1
Config Tool opens.
-
Select Initial.
-
In the Features section, only select the following:
-
Service Framework
-
Common Service
-
-
Select Run.
Historical
-
Sign in as a member of DNA Installers.
-
Start an elevated PowerShell session.
-
Run the following commands:
set-silo Historical
start-configtool.ps1
Config Tool opens.
-
Select Initial.
-
In the Features section, only select the following:
-
Service Framework
-
-
Select Run.
Inter-System Publish/Subscribe (ISPS)
-
Sign in as a member of DNA Installers.
-
Start an elevated PowerShell session.
-
Run the following commands:
set-silo ISPS
start-configtool.ps1
Config Tool opens.
-
Select Initial.
-
In the Features section, only select the following:
-
Service Framework
-
ISPS Service
-
-
Select Run.
Management of Change (MoC)
-
Sign in as a member of DNA Installers.
-
Start an elevated PowerShell session.
-
Run the following commands:
set-silo ManagementOfChange
start-configtool.ps1
Config Tool opens.
-
Select Initial.
-
In the Features section, only select the following:
-
Service Framework
-
Management Of Change (Common)
-
-
Select Run.
Remote Client Service (RCS)
-
Sign in as a member of DNA Installers.
-
Start an elevated PowerShell session.
-
Run the following commands:
set-silo RCS
start-configtool.ps1
Config Tool opens.
-
Select Initial.
-
In the Features section, only select the following:
-
Service Framework
-
RCS Service
-
-
Select Run.
RealTime
-
Sign in as a member of DNA Installers.
-
Start an elevated PowerShell session.
-
Run the following commands:
set-silo Realtime
start-configtool.ps1
Config Tool opens.
-
Select Initial.
-
In the Features section, only select the following:
-
Service Framework
-
SQL Engine
-
RealTime Service
-
OPC DA Server
-
Management of Change (Common)
-
Management of Change (RealTime)
-
-
Select Run.
Shared
-
Sign in as a member of DNA Installers.
-
Start an elevated PowerShell session.
-
Run the following commands:
set-silo Shared
start-configtool.ps1
Config Tool opens.
-
Select Initial.
-
In the Features section, only select the following:
-
ezXOS (Elements)
-
-
Select Run.
Tools
-
Sign in as a member of DNA Installers.
-
Start an elevated PowerShell session.
-
Run the following commands:
set-silo Tools
start-configtool.ps1
Config Tool opens.
-
Select Initial.
-
In the Features section, only select the following:
-
Tools (Common)
-
Tools (Administration)
-
-
Select Run.
Update ezXOS elements in the data root
The following procedure details how to update easy eXtended Operator Station (ezXOS) elements in the data directory (that is, %DNADataRoot%) on either the display source or the Display Edit Station (DES).
-
Sign in as a member of DNA Display Editors and DNA Display Users.
-
On the desktop, right-click the Windows Powershell for DNA shortcut, and then select Run as administrator.
Windows PowerShell for DNA opens.
-
Run the following commands:
set-silo ezxos
HMIDisplayEnvironmentTool.exe
The HMI Display Environment Tool opens and performs the following operations in sequence without any user interaction:
-
Migrates displays to the latest version (migratedsp.exe)
-
Initializes the edit database (loadeditdb.exe)
-
Converts DXF files to XEM files (convertdsp.exe)
-
Initializes the runtime database (xosloaddb.exe)
For further information on this tool, refer to "Preparing HMI Displays and Graphics Database" in the AVEVA Enterprise SCADA HMI Installer documentation.
-
-
Prior to opening eXtended Editor (XE) as a new user, proceed as follows:
-
On the desktop, double-click the Windows Powershell for DNA shortcut.
Windows PowerShell for DNA opens.
-
Run the following commands:
set-silo ezXOS
LoadEditDB
-
Service-oriented architecture (SOA) assemblies
New versions of the following Service-oriented architecture (SOA) assemblies are provided with this patch:
-
OASySDNA.MoC.Contracts.dll
-
OASySDNA.MoC.Skelta.Integration.dll
If you have AVEVA Work Tasks installed and configured on your system, proceed as follows:
-
Copy the above assembly files from the %DNAInstallRoot%\ManagementOfChange\bin\WorkTasksIntegration directory to the Orchestrator server under the C:\mocskeltaintegration directory.
For more information, refer to the AVEVA Work Tasks documentation.
Fixed issues
This following issues were fixed.
|
ID |
Description |
|---|---|
|
Case–N/A (Defect–3981626) |
This defect fix addresses an issue where the RealTime display composite DEVICE_ICONS_CMP.XEC was incompatible with AVEVA Enterprise SCADA HMI 2024 R2. Important: As part of this fix, the DEVICE_ICONS_CMP.XEM display was modified. You must re-load the display to resolve the issue. |
|
Case–960557583 (Defect–3871002) |
This defect fix addresses an issue where the Controller was unable to clear a point configured for re-alarming from the Alarm Summary window after the point returned to normal. |
|
Case–960563398 (Defect–3827192) |
This defect fix addresses an issue where the Operator Reminders application did not enable the Submit button in the Last Time section of the Add Reminder dialog after the Controller saved a new reminder. Important: As part of this fix, the CNTL_OPERATOR_REMINDER.XEM display was modified. You must re-load the display to resolve the issue. |
|
Case–960570338 (Defect–3941289) |
This defect fix addresses an issue where the AVEVA Enterprise SCADA Applications Virtual RTU Player responded incorrectly to an ABCIP Multistate/Valve command. |
|
Case–960575245 (Defect–3887100) |
This defect fix addresses an issue where the system did not behave as expected when a flexible text object subscribed to a RealTime database (RTDB) table that had neither dataset nor group fields. |
|
Case–960581277 (Defect–3900772) |
This defect fix addresses an issue where the Advanced Database Editor (ADE) "Clone Remote and Protocol" command did not set the Scan Remote Terminal Unit (RTU) for the Bristol Standard Asynchronous/Synchronous Protocol (BSAP). |
|
Case–960588136 (Defect–3931599) |
This defect fix addresses an issue where the PI Historical button was not retrieving records that existed in the PI Server. |
|
Case–960590185 (Defect–3916971) |
This defect fix addresses an issue where Open Platform Communication (OPC) remotes stopped polling. Important: If the problem persists, you can increase the value of the OPC_INITGROUP_HOLDOFF_SEC configuration setting. The default value is one second. |
|
Case–960604655 (Defect–3982383) |
This defect fix addresses an issue where the SQLEngine.oasoa process exited suddenly due to the OPC multistate record's output coordinate being set to NO_COMMAND. |
|
Case–960601278 (Defect–3990669) |
This defect fix addresses an issue where the system generated a validation error when an Administrator attempted to save a download list configuration in ADE with an array field as the database path. |
|
Case–960604716 (Defect–3993344) |
This defect fix addresses an issue where a TCPListener memory leak caused the application to become unresponsive. |
|
Case–960613164 (Defect–3986769) |
This defect fix addresses an issue where the system did not reevaluate a parent alarm suppression after the timeout value expired. |
|
Case–960615559 (Defect–4042298) |
This defect fix addresses an issue where the OPC Data Access (DA) server logged the following error in the oasErrLog file: Collection was modified; enumeration operation may not execute |
|
Case–960617029 and 960564238 (Defect–3986771 and 3900432) |
This defect fix addresses an issue where the system logged duplicate data errors during Datapump batch insertion. Important: As part of this fix, we have created the BULK_INSERT_DUPLICATE_ERRMSG_LOGGING configuration setting. For more information, refer to "All connection type configuration settings" in the AVEVA Enterprise SCADA Historical Administrator documentation. |
|
Case–960622120 (Defect–4029055) |
This defect fix addresses an issue where the XACTSpooler component would exit abruptly while processing empty strings during RealTime start up. |
|
Case–960622839 (Defect–4048505) |
This defect fix addresses an issue that caused dbll safeload and dbput to fail with an exception on the non-owning Decision Support System (DSS). |
|
Case–960636936 (Defect–4099702) |
This defect fix addresses an issue where multiple alarm suppression records could not be imported through the ADE Point Import utility. |
|
Case–960641642 (Defect–4081282) |
This defect fix addresses an issue where the appearance of ADE combobox objects varied depending on the launch method. |
|
Case–960648187 and 960656094 (Defect–4321509) |
This defect fix addresses an issue where the system ran the retrieval of a timer record's dataset against an invalid record. |
|
Case–960654917 (Defect–4321491) |
This defect fix addresses an issue where a device object displayed a command-in-progress FlexTag when its child points had no commands in progress. |
|
Case–960656458 (Defect–4117132) |
This defect fix addresses an issue where CMXPersistenceStore continuously logged error messages related to the prodtype table. |
|
Case–960668502 (Defect–4339765) |
This defect fix addresses an issue where adaptive replication exited suddenly on both owning and non-owning systems when updating a string within an array on the Hot owning RealTime server. |
|
Case–960671429 (Defect–4390157) |
This defect fix addresses an issue where ADE Export/Import from Excel did not complete successfully if the column labels were changed. |
|
Case–962612852 (Defect–4333670) |
This defect fix addresses an issue where the system generated incorrect Rate of Change (ROC) return-to-normal alarms. |
|
Case–962628736 (Defect–4375803) |
This defect fix addresses an issue where, when Store and Forward mode switches did not complete, the Store and Forward source system had no active mode. |
|
Case–962636519 (Defect–4351944) |
This defect fix addresses an issue where cmxrepsvr routes entered the disabled state. |
|
Case–962640973 (Defect–4558707) |
This defect fix addresses an issue where mode switch did not succeed when first attempted after system startup. Important: As part of this fix, we have created the MODE_SWITCH_ARBITRATION_CACHE_WAIT_TIME_MS configuration setting within the RealTime_ModeSwitch.json file. This setting enables you to modify the Mode Switch arbitration cache wait timeout. The default wait timeout is sufficient for small- to large-system deployments. For more information, refer to "Modify the mode switch wait timeout" in volume 1 of the AVEVA Enterprise SCADA RealTime Administrator documentation. |
|
Case–962658020 (Defect–4558694) |
This defect addresses an issue where the system generated "MALFORMED XML Errors" when the Extended Markup Language (XML) Protocol Driver for OASyS processed messages larger than 1024 bytes. |
|
Case–962660851 (Defect–4412097) |
This defect fix addresses an issue where the Station Summary window was unable to access an icon in the custom icon folder. Important: To support custom-defined icons, we have modified the GetIcon function included in
the following displays: If you have customized versions of these displays, you must manually migrate the modification of the GetIcon method to your displays. |
|
Case–962671044 (Defect–4462218) |
This defect fix addresses an issue where the easy eXtended Operator Station (ezXOS) exited abruptly during translation of the DROPMENU composite. Important: The DROPMENU.XEC composite file was modified as part of this fix. |
|
Case–962706058 (Defect–4529219) |
This defect fix addresses an issue where the Controller was unable to generate a Quick Trend as expected through a Control dialog. |
|
Case–962676547 (Defect–4422869) |
This defect fix addresses an issue where BLTHost.RealTimeTrend exceeded the warning limit for the handle count. |
|
Case–962752823 (Defect–4574855) |
This defect fix addresses an issue where certain directories were incorrectly listed in the antivirus exclusion list within the AVEVA Enterprise SCADA Security Administrator Guide. For further information, refer to "Exclude folders from antivirus scanning for AVEVA Enterprise SCADA" in the AVEVA Enterprise SCADA Security Administrator documentation. |
|
Case–962757284 (Defect–4617775) |
This defect fix addresses an where the Software Analyzer (SWANA) Translator reported "no translator available for ABDF1". |
|
Case–962719517 (Defect–4551761) |
This defect fix addresses an issue where the groupTOD table's TopOfDay field value was not properly replicated to non-owning systems. |
Known issues
The following known issues were open at the time of this release.
|
Description |
Workaround (if applicable) |
|---|---|
|
There is a known issue in AVEVA Enterprise SCADA 2025 Patch 1 wherein Developers are unable to compile the sample C++ Software Development Kit (SDK) projects on a development computer with Visual Studio installed. |
Contact AVEVA Customer Support to request copies of the missing CPP .props files. |
User documentation
For the AVEVA Enterprise SCADA 2025 Patch 1 release, only documentation that was directly affected by a defect fix is included. User documentation addendums are no longer included as part of patch deliverables.
If a document is not listed as updated in these notes, the existing AVEVA Enterprise SCADA 2025 documentation is still applicable.
The following AVEVA Enterprise SCADA documents contain updates and are included with this patch:
-
AVEVA Enterprise SCADA Release Notes (this document) (PDF)
-
AVEVA Enterprise SCADA Historical Administrator Guide (PDF)
-
AVEVA Enterprise SCADA RealTime Administrator Guide, Volume 1 (PDF)
-
AVEVA Enterprise SCADA Security Administrator Guide (PDF)
The latest versions of all the documentation are available on the AVEVA Documentation Portal and on the AVEVA Knowledge & Support Center.
To view the AVEVA Enterprise SCADA user documentation on the AVEVA Documentation Portal, sign in using your AVEVA product-support credentials (the same ones used for the AVEVA Knowledge & Support Center).