The proto_event table is part of the Remote Terminal Unit (RTU) Events and Alarms application. The records in the proto_event table help in classifying the different types of events generated by the RTU. The proto_event table contains the following internal fields:

Internal Field Name

Data Type

Description

almSev

sev_enum

The severity of the alarm.

configItem

GasC_configItem

The name of the parameter that will be changed.

evt_grp

protoEvtGrpslot

The name of the proto_event_grp record with which the proto_event will be grouped.

evtDest

pe_evt_dest

Indicates whether the event is applied to all runs or all streams, or to a particular run or stream.

evtmsg

string80

The event message to use for this particular event.

name

pntname

The unique name of this proto_event record.

objProb

oas_boolean_t

Send an event message to Measurement indicating that the event is problematic?

regnum

int

Either the point type number (the register number from the Remote Terminal Unit [RTU] as contained in the polled event) or the converted, custom format of the raw vector value returned from the RTU.

runNum

unsigned char

the run/stream number for the meter.

toAlarm

oas_boolean_t

Send evtmsg to the Alarm Summary window with the indicated Alarm Severity?

toConfig

oas_boolean_t

Update the configuration in Measurement when there is a configuration change in the device?

toEvent

oas_boolean_t

Send the event to the Operational Activities Summary window?

vectorstr

fieldname

Either the event type value in the polled event (converted to a text string) or the point type number (the register number from the RTU as contained in the polled event).