Please ensure Javascript is enabled for purposes of website accessibility
Powered by Zoomin Software. For more details please contactZoomin

AVEVA Enterprise SCADA

Trend

  • Last UpdatedJul 05, 2024
  • 2 minute read

The function of this Business Logic Tier (BLT) is to retrieve collection and summary data from the RealTime database (RTDB) collect table and the Historical database TimeSeries or timeline table.

  • The data returned includes the following columns:

  • Time is the collection time in Greenwich Mean Time (GMT) format.

  • Milliseconds is the collection time milliseconds.

  • Value is the summarized or collected value.

  • Status is the traditional data quality.

  • fieldTime is the field time in GMT format.

  • fieldMilliseconds is the field time milliseconds.

  • dqFlag is the position of the active data quality attribute with the highest precedence.

The value of dqFlag is determined by analyzing the attributes that are active in the dqFlags field in the provided table. In instances where the ExtendedDataQualityUnavailable attribute (position 12) is active, the dqFlag will be inferred from the traditional data quality following this conversion table:

NameStatus

dqFlag

Description

A

5

Point was in alarm.

M

19

Value was Manually edited or overriden.

O

9

Point was not actively being polled.

Q

2

The status of the point could not be determined during the value collection.

"."

0

Point was in normal status. No extended data quality attribute active.

Syntax

Trend <tablename> <tagname> <columnname> <starttime> <endtime> [showFieldTime]

Parameters

Name

Description

tablename

The name of the RTDB / Historical database table that contains the data to be accessed. This can be any of the following: collect, hour, day, month, year.

tagname

The name of the point to be viewed.

columnname

The column of the RTDB / Historical database tables to view. This can be any of the following: value, minimum, maximum, average. If the table name is collect, the only column allowed is the value column. If the table name is not collect, the value column is the instantaneous value of the point. (The value at the top of the hour).

starttime

The time from which to begin the trend data. This is entered as an integer representing Greenwich Mean Time (GMT) time, which is localized to your time zone.

endtime

The time at which the trend data stops. This is entered as an integer representing GMT time, which is localized to your time zone.

showFieldTime

If the table name is collect, enter 1 to display the field timestamp of the collection. Enter 0 or NULL to not display the field timestamp of the collection.

Example

Trend 'collect', 'analog.0analog.curval', 'value', 1401376140, 1401376320, 1

Time

Milliseconds

Value

Status

fieldTime

fieldMilliseconds

dqFlag

1401376140

0

2

O

1401376140

0

2

1401376200

0

30

A

1401376200

0

3

1401376260

0

10

1401376260

0

0

1401376320

0

15

M

1401376320

0

1

(4 rows affected)