To edit the target dialog box

  1. Log on as dnaInstaller.

  2. Navigate to %DNAInstallRoot%\ADE\config\ADE\DBEdit\Schema\baseline.

  3. Copy the file of the table that you want to modify to %DNADataRoot%\ADE\config\ADE\DBEdit\Schema\custom, and rename it to <TableName>.alter.xml.

  4. Add WritableTargetForm="true" to the desired field. You can remove any unmodified fields. For example:

    <Field Name="description"

    RowLabel="Description"

    ColumnLabel="Description"

    ToolTipText="Description of the record"

    TabOrder="20"

    IsRequired="false"

    IsReadOnly="false"

    IsVisible=" true"

    WritableTargetForm="true"

    DisplayWidthToUse="Maximum">

    </Field>

  5. On the desktop, double-click the Windows PowerShell for DNA shortcut.

    Windows PowerShell for DNA opens.

  6. Execute the following commands:

    set-silo ADE

    DBEditDisplaySchemaMerge

    You can now edit data in the target dialog box using the Advanced Database Editor (ADE).

  7. Where Remote and/or Remote_SSO is used, complete the following steps:

    1. Copy the newly compiled %DNADataRoot%\ADE\config\ADE\DBEdit\DBEditSchema.xml file to the target servers running Remote Client Service (RCS).

    2. Place this file in folder %DNADataRoot%\RCS\config\ADE\DBEdit.

      This folder location will exist if the system was prepared for Remote ADE operation.