Connection Row Edit: Line Error Suppression tab
- Last UpdatedApr 24, 2025
- 2 minute read
The Line Error Suppression tab in the connection Row Edit dialog box is used to enable No Reply alarm suppression for remotes on a particular connection.
Refer to the table below for field descriptions and instructions on how to configure the editable fields.

Items on the Line Error Suppression Tab in the Connection Row Edit Dialog Box
|
Items |
Description |
|---|---|
|
Enable Line Error Suppression |
Select Enable Line Error Suppression. |
|
Failed Remote Threshold |
Enter the number of remotes that must fail consecutively before the system generates a No Reply alarm. For example, assume the threshold is "3". If two remotes fail to reply during separate, consecutive polls, the system does not issue a No Reply alarm. Instead, it:
|
|
Count on-scan remotes only against failure threshold |
Select to include only onscan remotes in the no reply count. Scenario 1: Count on-scan remotes only against failure threshold not selected Assume that:
|
|
Enable Line Failure Alarms |
Select to have the system generate an alarm when the number of "No Reply" remotes reaches the configured threshold. |
|
Generate Persistent Alarms |
If desired, select to generate persistent alarms. |
|
Line Failure Alarm Severity |
Select the Line Failure Alarm Severity. |
|
Enable Return To Normal Alarms |
Select to have the system generate such an alarm when the line returns to normal operation. |
|
Return To Normal Alarm Severity |
Select the Return To Normal Alarm Severity. |
For further information, refer to No Reply Alarm Suppression.