Flowxfer table details

  • Last UpdatedApr 24, 2025
  • 3 minute read

The flowxfer table is used by the Product Transfer Checking application. This table contains information on product transfer relationships. The flowxfer table contains the following internal fields:

Internal Field Name

Data Type

Description

alarm_lastProducts

unsigned long

A unique number formed by the combination of the last two incompatible product's ptnums that triggered an alarm.

dataset

doas_dset_slot

This field indicates the dataset to which the record is assigned. Datasets are used to associate the record with the privileges assigned for each system mode. Once a record is assigned to a dataset value, the dataset can only be changed to a value for which the system has a privilege record.

description

description

A description of this Flow Transfer Checking point, up to 47 characters in length.

destination.downstreamZone

double

Volume upstream of the milepost or meter to gather product information.

destination.exclusionZone

double

Initial volume of the batch lineup on a meter that is excluded from the Product Compatibility checks.

destination.milepost

int

Milepost value used for pipeline location and pump destination types.

destination.reference

path

Path to a point in the RealTime database (RTDB) that represents the destination device.

destination.type

flowxferDestType

The type of destination.

destination.upstreamZone

double

Volume upstream of the milepost or meter to gather product information.

destination.zonemeasure

zoneMeasure

Time or Volume for upstream and downstream zones.

destination.controlDelay

int

Time interval (minutes) between commands sent to the device.

destination.flowxferStatus

path

The path to the status or multistate devices for the permissive section of Flow Transfer dialog box.

destination.cmdOn

IOspecString

The command offset for turning on status.

destination.cmdOff

IOspecString

The command offset for turning off status.

destination.tankGroupArray

tankGroupArray

Array of tanks to compare if destination.type is Tank Group.

DRA.autoShutdown

oas_boolean_t

Enable the sending of a command when a product violation is detected between a Drag Reducing Agent (DRA) source and destination?

DRA.shutdownCommand

string80

The command that is sent to the multistate or status point.

flag.alminh

oas_boolean_t

Prevent the generation of product violation alarms generated by the continuous monitor for this rule?

flag.cevinh

oas_boolean_t

Prevent the generation of an Historical event when a rule that was in violation is resolved?

flag.clrinh

oas_boolean_t

Prevent the generation of Return-to-Normal alarms when a rule that was in violation is resolved?

flag.evtinh

oas_boolean_t

Prevent the generation of an Historical event when a product violation is detected?

flag.bmsg

messageslot

The message associated with the record.

flag.priorityDisplay

modelname

The display associated with the Priority Display icon on an easy eXtended Operator Station (ezXOS) Control dialog.

flag.safety

oas_boolean_t

Is the point safety-related?

group

groupslot

This field shows the group that this point is associated with for alarming.

inh.admin

oas_boolean_t

Inhibit the monitoring of the flowxfer record altogether?

name

pntname

The unique name of this flowxfer record. The name can be up to 32 characters in length.

pumpRunningStates

string80

A string of values to represent which pump states are running.

pumpStoppedStates

string80

A string of values to represent which pump states are stopped.

source.milepost

int

This field is used for pipeline location and pump source types.

source.pumpPipeSegment

pipe_segmentslt

Pipe segment used to determine the last product for a pump type source.

source.reference

path

The path to a RealTime point that represents the source device.

source.type

flowxferSourceType

This field determines which fields are allowed and how the product transfer record will behave.

source.upstreamZone

double

Volume upstream of the milepost or meter to gather product information.

source.volThreshold

double

Tolerance volume for batch size difference checking.

valve

path

The path to a RealTime point that represents the valve controlling the association.

valveClosedStates

string80

A string of values to represent which states are closed.