AVEVA Enterprise SCADA

Recommended settings for IP cryout

  • Last UpdatedApr 24, 2025
  • 1 minute read
  • Use non-blocking mode

  • For the port on the Omnicomm side, set the Disconnect Level to "0".

  • For the port on the Remote Terminal Unit (RTU) side, set the Disconnect Level to "2".

  • Use Stale Data Threshold to discard data that has no client to receive it.

  • Use Idle Timeout at the port on the RTU side to ensure that, when the RTU becomes silent for a period of time, the OASyS DNA Socket Server Relay service automatically disconnects it.

  • The number of connection records that connect to the port should be equal to the number of RTUs crying out to the partner port.