Test results with the modified index

  • Last UpdatedApr 24, 2025
  • 1 minute read

CPU Time and Query Duration for the queries were extracted from the profiler results. CPU was monitored using the Windows Performance Monitor.

The following results are with the value and dataQuality added to the index in the TimeSeries Collect table.

Test Action

Max CPU %

Average CPU Time (milliseconds)

Average Duration (milliseconds)

readTimeSeriesCollect

10%

45

177

TimeSeries Collect row insertion

6%

1586

1649

TimeSeries

Collect row deletion

6%

1611

1758

Disk Space Requirements

The total index size, the number of rows, the disk space reserved, and the disk space used and unused by the collect table are described in the table below.

Name

Index Size

Rows

Reserved

Data

Unused

collect

49 GB

>725 million

87 GB

38 GB

1960 KB

The sizes of each index in the collect table are described in the table below.

Index Name

Index ID

Type

Type Description

Index Size

CollectTimeTagIdx

1

1

CLUSTERED

119 MB

CollectTagTimeIdx

2

2

NONCLUSTERED

27 GB

CollectTagFieldTimeIdx

3

2

NONCLUSTERED

22 GB