Connection table details
- Last UpdatedApr 24, 2025
- 4 minute read
The records in the connection table are used to define connections that are used to communicate with remote devices. The connection table contains the following internal fields:
|
Internal Field Name |
Data Type |
Description |
|---|---|---|
|
accessFlag |
displayname |
This flag is used by easy eXtended Operator Station (ezXOS) to determine whether a table is being modified through the Advanced Database Editor (ADE). If the flag is set, access to the table is denied. |
|
act_modem |
modemslot |
Active modem in use by the connection. |
|
act_sigcfg |
sigslot |
Active signal configuration. |
|
action |
connect_action |
Current connection action. |
|
broadcast |
Broadcast_table |
The broadcast table contains the commands which should be broadcast on the connection, and the specification requirements for broadcasting. This feature is often used for time synchronization and accumulator freeze commands. |
|
cid |
short |
Connection low-level identifier. |
|
cmode |
connect_mode |
Communication mode (for example, host poll). |
|
cnt_time |
unsigned short |
Maximum time to establish connection (sec). |
|
cnt_timeout |
unsigned short |
Maximum time without success (sec). |
|
cnt_good |
unsigned short |
The minimum connection time (in seconds) that was successful. It is assigned to a value to avoid bouncing back and forth between the primary connection, if communications are poor, and a good alternate connection. |
|
commproc |
commprocslot |
Connection’s Omnicomm process. |
|
comm_msg |
comm_msgQ |
Pending connection action queue. |
|
cfg_protocol |
description |
Protocol specific configuration. |
|
consta |
connstatus |
Current connection status. |
|
ctype |
connect_type |
Type of connection. |
|
curstate |
connect_state |
Current connection state. |
|
cur_stats |
connthruput |
Current throughput statistics. |
|
delay |
unsigned short |
Communications overhead delay period in milliseconds. |
|
description |
description |
Connection description |
|
device |
filename |
This field shows the host IP address. Typically, a logical name is assigned to it from the terminal_server table, so that the IP address changes during a failover to an alternate service, site, or system. |
|
df1DLink.ackdly |
unsigned short |
The maximum time (in milliseconds) to wait for a reply to a query (protocol-specific). |
|
df1DLink.duplex |
abdf1duplex |
The DF1 protocol driver session layer operation mode (protocol-specific). |
|
df1DLink.errcheck |
abdf1errcheck |
The driver error detection algorithm used by the Remote Terminal Unit (RTU). This field is protocol-specific. |
|
df1DLink.gatewayAdrs |
abdf1remoteaddr |
The address of the gateway used for communication (protocol-specific). |
|
df1DLink.gatewayType |
abdf1GtwyType |
The type of gateway used to connect with the remote (protocol-specific). |
|
df1DLink.host_addr |
abdf1remoteaddr |
The station address for the AVEVA Enterprise SCADA host (protocol-specific). |
|
dft_sigcfg |
sigslot |
Default signal configuration. |
|
dialFailStats |
failCntStats |
The statistics of dial connection failure. |
|
dialMaxFailCnt |
unsigned char |
Maximum number of consecutive dial connection failures. |
|
disable_onscan_remote_check |
oas_boolean_t |
Include only onscan remotes in the no reply count? |
|
dretry |
unsigned char |
The number of retries for dial/cryout. |
|
enable_line_error_suppresion |
oas_boolean_t |
Enable No Reply alarm suppression for remotes on a connection. |
|
enable_line_failure_alarms |
oas_boolean_t |
Have the system generate an alarm when the number of "No Reply" remotes reaches the configured threshold? |
|
enable_line_normal_alarms |
oas_boolean_t |
Have the system generate an alarm when the line returns to normal operation? |
|
flag |
flags |
For information on the flag structure, see Flag structure details. |
|
FEPenb |
oas_boolean_t |
Is the connection front-end processing enabled? The action of this field is protocol specific. |
|
group |
groupslot |
The group that this point is associated with for alarming. |
|
in_alm |
oas_boolean_t |
Is the connection in general alarm (for example, communication failure)? |
|
intg_update |
oas_boolean_t |
Is integrity scan set when the connection is established? |
|
intr_rtu_delay |
unsigned short |
Expected delays for communication media (for example, satellites which have inherent delays). |
|
last_bad |
internaltime |
The last bad status time. |
|
last_fail |
internaltime |
The connection failure time. |
|
last_good |
internaltime |
The last good status time. |
|
lastOwnState |
oas_boolean_t |
The previous own state. |
|
last_rest |
internaltime |
The connection established time. |
|
lastRollupTime |
internaltime |
The time of the last rollup. |
|
mappingFlag |
unsigned int |
The 32-bit integer value used to map this point to a non-AVEVA Enterprise SCADA system. |
|
modeSwitchTime |
internaltime |
This field indicates the time of a mode switch. |
|
modeTimeout |
long |
The mode switch timeout (milliseconds). |
|
mpc_time |
unsigned short |
The minimum time duration from the beginning of one host poll cycle to the next. |
|
name |
pntname |
The unique name of this connection record. The name can be up to 32 characters in length. |
|
noreply_remote_count |
unsigned int |
The number of remotes that must fail consecutively before the system generates a No Reply alarm. |
|
num_pc |
unsigned char |
The minimum number of poll cycles on temporary dial connection before releasing a modem. |
|
onscan |
oas_boolean_t |
Is the connection onscan? |
|
persistent_line_failure_alarm |
oas_boolean_t |
Generate persistent alarms? |
|
pointClass |
configenumslot |
The Point Class category contains multiple configuration enumerations used for categorical configuration of points. |
|
pointSubClass |
configenumslot |
Point Sub Class is a configurable enumeration category used for categorical configurations, but you cannot use this for configurable alarms and events. |
|
prv_percnt |
float |
A structure that stores the previous percent-throughput statistics for this connection. |
|
port |
unsigned int |
The port number to use on a network device. |
|
pnd_rsrv |
oas_boolean_t |
Is the pending modem reserved? |
|
ptnum |
unsiged char |
This field represents the record’s slot number in the database. |
|
pref_bank |
bankslot |
Preferred modem bank to use. |
|
proto |
protocolslot |
Connection protocol. |
|
retry |
unsigned char |
The number of times that the system Host should retry to obtain data from a remote if the initial query fails. |
|
recnt_delay |
unsigned short |
Reconnection delay time (sec). |
|
severity_line_failure_alarms |
sev_enum |
The line failure alarm severity. |
|
severity_line_normal_alarms |
sev_enum |
The return to normal alarm severity. |
|
telno |
description |
Telephone number string for a dialup line. |
|
telwait |
unsigned short |
Time, in seconds, to wait for a connection to be established. |
|
temp_con_delay |
unsigned int |
Delay between temporary connections. |
|
tmpLink |
oas_boolean_t |
Is the connection temporary? |
|
mappingFlag |
unsigned int |
The 32-bit integer value used to map this point to a non-AVEVA Enterprise SCADA system. |
|
udp_source_enable |
oas_boolean_t |
If ctype is Network UDP, you can optionally select this checkbox to configure the local transport address (port number), which could be different than the remote port number. |
|
udp_source_port |
unsigned int |
The port number on which the AVEVA Enterprise SCADA host listens for responses from remotes on the connection. |
|
persistentSocket |
oas_boolean_t |
This field specifies whether the connection's socket remains connected when it is not the primary connection for a given remote. The default value is false. |