Configure separate alarm limits
- Last UpdatedApr 24, 2025
- 1 minute read
You can configure separate High, Low, HighHigh, and LowLow alarm limits for an analog, a rate, a flowTotalConfig, or a gascontract point by using the point's Alarm Limits dialog.
Note: In the following procedure, an analog point is used as an example. The procedure is the same for rate and gascontract points, but slightly different for flowTotalConfig points (as described in the procedure). The Analog Alarm Limits dialog is opened through the Analog Control dialog. For more information on Control dialogs, see the AVEVA Enterprise SCADA HMI Controller documentation.
To configure separate alarm limits
-
Open the Analog Control dialog.
-
Select Alarm Limits.
Note: On the Flow Total Control dialog, select the appropriate Limits button.
The Analog Alarm Limits dialog appears.

-
In the High, Low, HighHigh, and LowLow sections, clear or select the Enabled checkboxes as desired.
-
Depending on your choices in step 4, enter alarm limits in the High, Low, HighHigh, and/or LowLow fields.