AVEVA Enterprise SCADA

AlmSevOverride table details

  • Last UpdatedApr 24, 2025
  • 2 minute read

The Alarm Severity Override (almSevOverride) table is used to match alarm criteria and override alarm behaviour for matched alarms.

You can match alarms based upon the following:

  • Message text

  • Table

  • Process

  • Host name

Alarms must match all configured criteria.

You can also override the alarm severity for all alarm types (Application, System, Database).

With System alarms, you can do the following:

  • Override the following additional information on the alarm:

    • Category

    • Group

    • Station

      • When Override Station is selected, and a station is configured, then the alarms matching the criteria are rolled up to the station, site, and region. For more information, refer to the AVEVA Enterprise SCADA RealTime Controller documentation.

  • Either inhibit the alarm, or route it to a third-party application.

The almSevOverride table contains the following internal fields:

Internal Field Name

Data Type

Description

description

pntdescription

This field specifies a description of the record up to 47 characters in length.

matchMessage

alsumMsg

This field allows for matching the alarm by the alarm message.

matchTable

string48

This field allows for matching the alarm by the table name.

matchProcess

string48

This field allows for matching the alarm by the process name.

matchHost

pntname

This field allows for matching the alarm by the host name generating the alarm.

doModifySeverity

oas_boolean_t

Override the severity of the alarm?

severity

sev_enum_email

This field specifies the new severity to assign to the alarms matching the criteria. This applies to all alarm types.

doModifyGroup

oas_boolean_t

Override the group for System alarms?

groupToModify

groupslot

This field specifies the new group to assign to the alarms matching the criteria. This field applies to System alarms.

doModifyCategory

oas_boolean_t

Override the category for System alarms?

category

pntname

This field specifies the new category to assign to the alarms matching the criteria. This field applies to System alarms.

doModifyStation

oas_boolean_t

Override the station for System alarms?

station

stationslot

This field specifies the new station to assign to the alarms matching the criteria. This field applies to System alarms.

ptnum

slot

This field represents the slot number of the record in the database.

accessFlag

Displayname

This flag is used by the easy eXtended Operator Station (ezXOS) to determine whether a table is being modified through the Advanced Database Editor (ADE). If the flag is set, access is denied.

mockey

GUIDstring

This flag specifies a unique key for this record to enable Management of Change (MoC) synchronization.

publishSystemAlarm

oas_boolean_t

This field indicates whether or not to publish the System alarm.

systemAlarmTopic

string64

This field specifies the name of the PubSub key topic on which to publish the System alarm.

inhibitSystemAlarm

oas_boolean_t

Inhibit any matching System alarms?

Related Links