AlmSevOverride table details
- Last UpdatedApr 24, 2025
- 2 minute read
The Alarm Severity Override (almSevOverride) table is used to match alarm criteria and override alarm behaviour for matched alarms.
You can match alarms based upon the following:
-
Message text
-
Table
-
Process
-
Host name
Alarms must match all configured criteria.
You can also override the alarm severity for all alarm types (Application, System, Database).
With System alarms, you can do the following:
-
Override the following additional information on the alarm:
-
Category
-
Group
-
Station
-
When Override Station is selected, and a station is configured, then the alarms matching the criteria are rolled up to the station, site, and region. For more information, refer to the AVEVA Enterprise SCADA RealTime Controller documentation.
-
-
-
Either inhibit the alarm, or route it to a third-party application.
The almSevOverride table contains the following internal fields:
|
Internal Field Name |
Data Type |
Description |
|---|---|---|
|
description |
pntdescription |
This field specifies a description of the record up to 47 characters in length. |
|
matchMessage |
alsumMsg |
This field allows for matching the alarm by the alarm message. |
|
matchTable |
string48 |
This field allows for matching the alarm by the table name. |
|
matchProcess |
string48 |
This field allows for matching the alarm by the process name. |
|
matchHost |
pntname |
This field allows for matching the alarm by the host name generating the alarm. |
|
doModifySeverity |
oas_boolean_t |
Override the severity of the alarm? |
|
severity |
sev_enum_email |
This field specifies the new severity to assign to the alarms matching the criteria. This applies to all alarm types. |
|
doModifyGroup |
oas_boolean_t |
Override the group for System alarms? |
|
groupToModify |
groupslot |
This field specifies the new group to assign to the alarms matching the criteria. This field applies to System alarms. |
|
doModifyCategory |
oas_boolean_t |
Override the category for System alarms? |
|
category |
pntname |
This field specifies the new category to assign to the alarms matching the criteria. This field applies to System alarms. |
|
doModifyStation |
oas_boolean_t |
Override the station for System alarms? |
|
station |
stationslot |
This field specifies the new station to assign to the alarms matching the criteria. This field applies to System alarms. |
|
ptnum |
slot |
This field represents the slot number of the record in the database. |
|
accessFlag |
Displayname |
This flag is used by the easy eXtended Operator Station (ezXOS) to determine whether a table is being modified through the Advanced Database Editor (ADE). If the flag is set, access is denied. |
|
mockey |
GUIDstring |
This flag specifies a unique key for this record to enable Management of Change (MoC) synchronization. |
|
publishSystemAlarm |
oas_boolean_t |
This field indicates whether or not to publish the System alarm. |
|
systemAlarmTopic |
string64 |
This field specifies the name of the PubSub key topic on which to publish the System alarm. |
|
inhibitSystemAlarm |
oas_boolean_t |
Inhibit any matching System alarms? |