Control the display of safety-related alarm and event messages
- Last UpdatedApr 24, 2025
- 1 minute read
Note: For information on overriding default configuration settings, refer to Modify configuration settings.
Follow the procedure below to configure the system such that, when a Controller selects the Safety Related checkbox on either the Alarm Summary or Event Summary window, the window displays one of the following:
-
Alarms/events associated with points designated as safety-related
-
Alarms/events that occur when safety-related points enter a safety-related alarm state
-
Alarms/events associated with both Safety Related points and Safety states
To control the display of safety-related alarm and event messages
-
In the %DNADataRoot%\RealTime\config\Settings directory, either create or open the RealTime_SafetyRelated.json file.
The following example shows the content of the RealTime_SafetyRelated.json file:
{
"RealTime": {
"ENABLE_SAFETY_FLAG": "BOTH"
}
}
-
For the "ENABLE_SAFETY_FLAG" value, do one of the following:
-
To have the Alarm or Event Summary window display only alarms associated with safety-related points when the Controller selects the Safety Related checkbox, change the value to POINT.
-
To have the Alarm or Event Summary window display only alarms associated with safety-related alarm states when the Controller selects the Safety Related checkbox, change the value to STATE.
-
To have the Alarm or Event Summary window display alarms associated with both safety-related points and safety-related alarm states when the Controller selects the Safety Related checkbox, change the value to BOTH.
-
To disable the safety-related alarm/event feature, change the value to NONE.
-
-
Save the file.
-
Restart the RealTime service.