AVEVA Enterprise SCADA

AddSYSalarm

  • Last UpdatedApr 24, 2025
  • 2 minute read

The function of this Business Logic Tier (BLT) is to add a RealTime service system alarm to the database.

Syntax

AddSYSalarm <key> <category> <messagetxt> <persistent> <flashing> <severity> <purgetimer> <group> <timestamp> <msec> [<host>]

Note: The above is entered as one line of syntax. The RealTime database (RTDB) must be open before calling AddSYSalarm. Use VDB.OpenDatabase() to open the RTDB.

Parameters 

Name

Description

key

A reference key for toggling the inalarm state of an alarm summary entry.

category

The category to which the alarm belongs. This can be arbitrary. This is used to distinguish similar alarms. The category must be one word without spaces.

messagetxt

Alarm message to be displayed.

persistent

This indicates whether or not the alarm remains in the alarm summary after acknowledgement and purge.

flashing

Indicates whether or not the point should be flashing.

severity

Alarm severity: low, medium, or high.

purgetimer

The purge timer is expressed in seconds. The timer starts after the alarm is acknowledged. The alarm is purged from the almsum table if the purge time has expired, and the persistent flag is "no".

group

The group name.

timestamp

The timestamp of the alarm, added in the format of number of seconds since January 1, 1970, 00:00 Greenwich Mean Time (GMT).

msec

Millisecond value of the timestamp.

host

The name of the host generating the alarm.

 

Example

The following adds a test system alarm:

AddSYSalarm "test1" "low_alarm" "test system alarm" "no" "yes" "low" 10 "" 12345 "radserv1"

Comments

Alarms generated solely by executing this Remote Procedure Call (RPC) are transient unless additional RealTime service processing is performed.

The host is optional, but the timestamp and msec parameters are required.