AVEVA Enterprise SCADA

MsgInfo table details

  • Last UpdatedApr 24, 2025
  • 1 minute read

The msgInfo table groups together a unique set of msgInfo records and allows alarm and event messages to be modified. The msgInfo table contains the following internal fields:

Internal Field Name

Data Type

Description

name

string48

This field specifies the name of the msgInfo record.

Note: If the message text should be retrieved from the satellite resource assembly, the value of this field must be equal to the name of the string resource defined in that assembly.

msgInfoSet

pntname

This field specifies the name of the msgInfoSet used to group together msgInfo records.

msgInfoSetAndName

string80

This field defines the unique name of the msgInfo record. This unique name is a combination of the msgInfoSet field and the name field.

msgText

string120

This field displays the message text to use when the useAssembly field is set to false.

useAssembly

oas_boolean_t

When this field is set to True, the message text is retrieved from a satellite resource assembly.

baseName

string120

This field displays the root name of the RESX file without its extension.

severity

sev_enum_email

This field displays the severity used for transient alarms and events.

ptnum

slot

This field represents the slot number of the record in the database.

accessFlag

displayname

This flag is used by the easy eXtended Operator Station (ezXOS) to determine whether a table is being modified through the Advanced Database Editor (ADE). If the flag is set, access is denied.