Please ensure Javascript is enabled for purposes of website accessibility
Powered by Zoomin Software. For more details please contactZoomin

AVEVA Enterprise SCADA

Reset the deviation limits

  • Last UpdatedApr 24, 2025
  • 1 minute read

Note: For information on overriding default configuration settings, refer to Modify configuration settings.

If an Administrator sets the RealTime .json file key CREEP_LSTDEV_FOLLOW_SP to yes, analog setpoints will reset the creep limits for a point. This helps to avoid the generation of false alarms.

To reset the deviation limits

  1. In the %DNADataRoot%\RealTime\config\Settings directory, either create or open the RealTime_DeviationsLmtsReset.json file.

  2. In the following line, change the value from no to yes.

    {

    "RealTime": {

    "CREEP_LSTDEV_FOLLOW_SP": "yes"

    }

    }

  3. Save the file.

  4. Restart the RealTime service.