Please ensure Javascript is enabled for purposes of website accessibility
Powered by Zoomin Software. For more details please contactZoomin

AVEVA Enterprise SCADA

Almlimitset table details

  • Last UpdatedApr 24, 2025
  • 1 minute read

The almlimitset table is used by the Alternate Alarm Limits application. Records in the almlimitset table group together the alternative alarm limits that exist for a specific point. The almlimitset table contains the following internal fields:

Internal Field Name

Data Type

Description

activeAlmLimit

pntname

The name of the almlimit record whose alarm limits you want to use for this alarm limit set.

dataset

doas_dset_slot

This field indicates the dataset to which the record is assigned. Datasets are used to associate the record with the privileges assigned for each system mode. Once a record is assigned to a dataset value, the dataset can only be changed to a value for which the system has a privilege record.

description

description

A description of the point, up to 47 characters in length.

group

groupslot

Many records have this field. A group is assigned to all points that are closely related.

msPnt

multistateslot

The name of the multistate point whose state message text determines which almlimit record becomes active.

name

pntname

The name of the almlimitset record.

useMsPnt

oas_boolean_t

Have an associated analog, rate, or flowTotalConfig point use a specific set of alternative alarm limits when msPnt enters the state specified in the almlimit table's state field (refer to Almlimit table details).