AVEVA Enterprise SCADA

Configure the number of spooler transaction calls

  • Last UpdatedApr 24, 2025
  • 1 minute read

Note: For information on overriding default configuration settings, refer to Modify configuration settings.

The spooler can be configured to call one or multiple stored procedures, which in turn add new device-based data to the Historical database. The DEVICE_BASED_HISTORY_BATCH_SIZE key determines the maximum number of stored procedures one spooler transaction calls. The default is 20: one spooler transaction takes care of up to 20 device-based data records. For performance reasons, you can change this value. The performance depends largely on RAM space: if RAM is low, the optimal batch size might be closer to 5 than 20.

To configure the number of spooler transaction calls

  1. In the %DNADataRoot%\RealTime\config\Settings directory, either create or open the RealTime_Collect.json file.

  2. In the following line, change the value to the desired number of spooler transaction calls:

    "RealTime" > "DEVICE_BASED_HISTORY_BATCH_SIZE": 20

  3. Save the file.

  4. Restart the RealTime service.