AlarmProcedure Row Edit: Filters tab
- Last UpdatedApr 24, 2025
- 3 minute read
As alarms do not have unique identities in AVEVA Enterprise SCADA, procedures are linked to alarms through a series of filters via the Filters tab in the alarmProcedure Row Edit dialog box. These filters allow you to target a single alarm, or a group of alarms, to be associated with a procedure that instructs Controllers on how to correctly respond to an alarm.
Refer to the table below for field descriptions and instructions on how to configure the editable fields.

Items on the Filters Tab in the alarmProcedure Row Edit Dialog Box
|
Item |
Description |
|---|---|
|
Name |
Select (...) and select the name of the alarmProcedure record from the Alarm Procedure Select dialog box. |
|
Description |
Enter a description of the record. The Description can be up to 47 characters in length. This field is for information purposes only and can be used to describe the record, its association with other points, or any other textual information. The Name and Description configured for a record appear in the summary tables in easy eXtended Operator Station (ezXOS). |
|
URL |
Enter the absolute or relative URL for the procedure to be opened. The URL can be up to 255 characters in the length. |
|
Enable Severity Filter |
Optional: Select to include procedures matching the Severity Filter value in the list of procedures shown in ezXOS for a given alarm. |
|
Severity Filter |
Optional: Select the severity of the alarm that will cause the system to show the procedure in ezXOS. |
|
Table Name Filter |
Optional: Enter an optional full or table point name for which the procedure applies. This field can be up to 255 characters in length and may contain wildcard filter criteria (*). Note: The Table Name Filter field will default to * when creating a new record. |
|
Point Name Filter |
Optional: Enter an optional full or partial point name for which the procedure applies. This field can be up to 255 characters in length and may contain wildcard filter criteria (*). Note: The Point Name Filter field will default to * when creating a new record. |
|
Category Filter |
Optional: Enter an optional full or partial category for which the procedure applies. This field can be up to 255 characters in length and may contain wildcard filter criteria (*). Note: The Category Filter field will default to * when creating a new record. |
|
Alarm Message Filter |
Optional: Enter an optional full or partial alarm message for which the procedure applies. This field can be up to 255 characters in length and may contain wildcard filter criteria (*). Note: The Alarm Message Filter field will default to * when creating a new record. |
|
Enable Safety Condition Filter |
Optional: Select to indicate whether procedures matching the Safety Condition Filter value should be included in ezXOS for any given alarm. |
|
Safety Condition Filter |
Optional: Select one of the following:
|