Status point configuration
- Last UpdatedApr 24, 2025
- 2 minute read
The status input/output points are configured through the Input/Output tabs in the status Row Edit dialog box, respectively. For full information on the status table, refer to volume 1 of the AVEVA Enterprise SCADA RealTime Administrator documentation.
Protocol-specific Fields
|
Field |
Description |
|---|---|
|
Bit Number |
Enter the bit address in decimal format. Note: The Output tab in the status Row Edit dialog box does not have a Bit Number field. If applicable, specify the bit number in the Coordinate field as follows: WordNumn or <FileType><FileNumber>:<WordNumn>\n Where:
|
Status configuration (example)
|
Field |
Input tab in the status Row Edit dialog box |
Output tab in the status Row Edit dialog box |
||
|---|---|---|---|---|
|
Bit 0 |
Bit 1 |
Bit 2 |
Bit 3 |
|
|
Coordinates |
B123:100 |
B123:100 |
B123:100\2 |
B123:100\3 |
|
Bit Number |
0 |
1 |
N/A |
N/A |
Input Bit 1 Coordinates uses the Bit Type File 123, and reads word 100 and bit 0.
Input Bit 2 Coordinates uses the Bit Type File 123, and reads word 100 and bit 1.
Output Bit 1 Coordinates uses the Bit Type File 123, and writes word 100 and bit 2.
Output Bit 2 Coordinates uses the Bit Type File 123, and writes word 100 and bit 3.
Note: The Coordinates specification for the input does not indicate which bit to read from the word. Therefore, you must configure the Bit Number field in the Input tab (refer to volume 1 of the AVEVA Enterprise SCADA RealTime Administrator documentation).
Control mnemonics requiring bit number specification
|
File type |
Control mnemonic |
Requires bit number specification? |
Example |
|---|---|---|---|
|
Timer |
EN, TT, DN |
No |
T20:4.TT |
|
PRE, ACC |
Yes |
T20:4.ACC/4 |
|
|
Counter |
CU, DC, DN, OV, UN |
No |
C20:4.DN |
|
PRE, ACC |
Yes |
C20:4.ACC/4 |
|
|
Control |
EN, EU, DN, EM, ER, UL, IN, FD |
No |
R20:4.UL |
|
LEN, POS |
Yes |
R20:4.LEN/4 |