AVEVA Enterprise SCADA

Delay the On/Off Delay Alarm Icon Behavior

  • Last UpdatedApr 24, 2025
  • 1 minute read

Note: For information on overriding default configuration settings, refer to Modify configuration settings.

You can delay the flag.alarm field and alarm bell icon from changing instantly when using the On/Off Delay enhancement. When enabled, the alarm icon indication will also be delayed with the alarm entry reported in the alarm summary, as specified by the value for On/Off Delay settings.

Note: The setting is disabled by default and applies only to analog and rate points.

To delay the On/Off Delay alarm icon behavior

  1. In the %DNADataRoot%\RealTime\config\Settings directory, either create or open the RealTime_FlagAlarmDelay.json file:

    {

    "RealTime": {

    "DELAY_FLAGALARM_ONOFFDELAY": false

    }

    }

  2. Change the value from false to true.

  3. Save the file.

  4. Restart the RealTime service.