The almlimit table is used by the Alternate Alarm Limits application. Each record in the almlimit table contains a set of alternative alarm limits referenced by an almlimitset record. The almlimit table contains the following internal fields:

Internal Field Name

Data Type

Description

configuredInhibits

stateInhibits

A structure of information about the point's alternative alarm limits that apply to analog, rate, and flowTotalConfig points.

configuredLimits

almlimitsettings

A structure of information about the state-based alarm inhibits.

dataset

doas_dset_slot

This field indicates the dataset to which the record is assigned. Datasets are used to associate the record with the privileges assigned for each system mode. Once a record is assigned to a dataset value, the dataset can only be changed to a value for which the system has a privilege record.

description

description

A description of the point, up to 47 characters in length.

group

groupslot

Many records have this field. A group is assigned to all points that are closely related.

memberOfSet

almlimitsetslot

The name of the almlimitset record that uses the alternative alarm limits configured in the almlimit record.

name

pntname

The name of the almlimit record.

state

pntname

The state of the associated multistate point that causes an analog, a rate, or a flowTotalConfig point to use the alternative alarm limits.

configuredInhibits.inh_dev

oas_boolean_t

Inhibit Creep state alarming?

configuredInhibits.inh_flat

oas_boolean_t

Inhibit Flatline state alarming?

configuredInhibits.inh_hi

oas_boolean_t

Inhibit High state alarming?

configuredInhibits.inh_hihi

oas_boolean_t

Inhibit HighHigh state alarming?

configuredInhibits.inh_lo

oas_boolean_t

Inhibit Low state alarming?

configuredInhibits.inh_lolo

oas_boolean_t

Inhibit LowLow state alarming?

configuredInhibits.inh_roc

oas_boolean_t

Inhibit Rate of Change (ROC) state alarming?

configuredInhibits.inh_setcreep

oas_boolean_t

Inhibit Setpoint Creep state alarming?

configuredInhibits.inh_creep_plus

oas_boolean_t

Inhibit Positive Creep alarming?

configuredInhibits.inh_creep_neg

oas_boolean_t

Inhibit Negative Creep alarming?

configuredInhibits.inh_nel

oas_boolean_t

Inhibit Normal Empty Level alarming?

configuredInhibits.inh_nfl

oas_boolean_t

Inhibit Normal Fill Level alarming?

configuredInhibits.inh_RR

oas_boolean_t

Inhibit Rate Reasonability alarming?

configuredInhibits.inh_uhi

oas_boolean_t

Inhibit User High alarming?

configuredInhibits.inh_ulo

oas_boolean_t

Inhibit User Low alarming?

configuredInhibits.inh_inst_hi

oas_boolean_t

Inhibit instrumentation failure high alarming?

configuredInhibits.inh_inst_lo

oas_boolean_t

Inhibit instrumentation failure low alarming?

configuredInhibits.inh_inst_rtu

oas_boolean_t

Inhibit instrumentation failure RTU alarming?

configuredLimits.creepDevLim

float

The maximum deviation value (EGUs) that is acceptable before calibration deteriorates.

configuredLimits.creepDevLimEnabled

oas_boolean_t

Enable the Creep Detection alarm?

configuredLimits.deltatime

long

The time interval over which the system should calculate the ROC.

configuredLimits.flattimeout

unsigned short

The maximum amount of time (in minutes) that can pass without an analog, a rate, or a flowTotalConfig value changing.

configuredLimits.flattimeoutEnabled

oas_boolean_t

Enable Flatline Alarming?

configuredLimits.hilim

float

The High alarm limit.

configuredLimits.hilimEnabled

oas_boolean_t

Enable High alarm limits?

configuredLimits.hihilim

float

The HighHigh alarm limit.

configuredLimits.hihilimEnabled

oas_boolean_t

Enable HighHigh alarm limits?

configuredLimits.lolim

float

The Low alarm limit.

configuredLimits.lolimEnabled

oas_boolean_t

Enable Low alarm limits?

configuredLimits.lololim

float

The LowLow alarm limit.

configuredLimits.lololimEnabed

oas_boolean_t

Enable LowLow alarm limits?

configuredLimits.negroclim

float

The maximum, negative allowable ROC (EGUs per second).

configuredLimits.roclim

float

The maximum, positive allowable ROC (Engineering Units (EGUs) per second).

configuredLimits.roclimEnabed

oas_boolean_t

Enable the ROC alarm?

configuredLimits.roc_method_used

ROC_method

The method to use in calculating the ROC.

configuredLimits.sptlolim

float

The lowest setpoint that can be issued.

configuredLimits.spthilim

float

The highest setpoint that can be issued.

configuredLimits.setCreeplimEnabled

oas_boolean_t

Enable the Setpoint Creep alarm?

configuredLimits.setCreeplim

float

The system generates an alarm when the current value of an analog point deviates this much beyond the commanded setpoint.

configuredLimits.lololimEnabled

oas_boolean_t

Enable the low low alarm limit.

configuredLimits.nellimEnabled

oas_boolean_t

Enable or disable normal empty level alarming.

configuredLimits.nellim

float

Normal empty alarm limit.

configuredLimits.nfllimEnabled

oas_booleat_t

Enable or disable normal fill limit alarming.

configuredLimits.nfllim

float

Normal fill alarm limit.