Almlimit Row Edit: Analog Limits tab

  • Last UpdatedApr 24, 2025
  • 1 minute read

Use the Analog Limits tab in the almlimit Row Edit dialog box to configure the point's alternative alarm limits that apply to analog points only.

Refer to the table below for field descriptions and instructions on how to configure the editable fields.

Important: When you configure or modify the alarm limits on the Analog Limits tab, the system transfers the settings to the corresponding limits of all analog records associated with the almlimit record. Similarly, when you configure or modify the alarm limits of an analog record associated with an almlimit record, the system transfers the settings to the almlimit record as well as any other analog records associated with that almlimit record.

Item

Description

Setpoint Low Limit

Enter the lowest setpoint that can be issued.

Setpoint High Limit

Enter the highest setpoint that can be issued.

Setpoint Creep Detection Enabled

Select to enable the Setpoint Creep alarm. When the current value of an analog point deviates too far from the commanded setpoint, the system generates an alarm.

Setpoint Creep Deviation Limit

When the current value of an analog point deviates this much beyond the commanded setpoint, the system generates an alarm.