The Device Rollup (DeviceRollupMonitor) application uses device table records to define field devices.
|
Internal Field Name |
Data Type |
Description |
|---|---|---|
|
curval |
longstring |
The value of the master point as specified in the DevPathJoin table. |
|
dataset |
doas_dset_slot |
This field indicates the dataset to which the record is assigned. Datasets are used to associate the record with the privileges assigned for each system mode. Once a record is assigned to a dataset value, the dataset can only be changed to a value for which the system has a privilege record. |
|
description |
description |
A description of this device point, up to 47 characters in length. |
|
flag.alarm |
oas_boolean_t |
Is the device, or any member of the device record, in an alarm state? |
|
flag.alminh |
oas_boolean_t |
Prevent off-normal alarms from being generated when a sequence fails to complete successfully? |
|
flag.bmsg |
messageslot |
The message associated with the record. |
|
flag.error |
oas_boolean_t |
Is any member of the device record that contributes to data quality rollup in an error state? |
|
flag.fresh |
oas_boolean_t |
Is the data update fresh for all members of the device contributing to data quality? |
|
flag.flexTag |
string |
The current flex tag hash associated with the device. |
|
flag.manl |
oas_boolean_t |
Is any member of the device record that contributes to data quality rollup in manual override mode? |
|
flag.offscan |
oas_boolean_t |
Is any member of the device record that contributes to data quality rollup off scan? |
|
flag.severity |
unsigned char |
The severity level of the alarm. |
|
flag.state_inhibited |
oas_boolean_t |
Is any member of the device record that contributes to data quality inhibited? |
|
flag.tag |
tagattr |
The tag attribute associated with the device. |
|
flag.testmode |
oas_boolean_t |
Is any member of the device record that contributes to data quality rollup in test mode and therefore suppressing alarms? |
|
group |
groupslot |
This field shows the group that this point is associated with for alarming. |
|
name |
pntname |
The unique name of this device record. The name can be up to 31 characters in length. |
|
ptnum |
slot |
This field represents the slot number of the record in the database. |
|
timestamp |
internaltime |
The last time the device record was processed due to a change in a member of the device record. |