Configure zero as a normal state
- Last UpdatedApr 24, 2025
- 1 minute read
Note: For information on overriding default configuration settings, refer to Modify configuration settings.
When using absolute alarming checking, a value of zero can be considered as in a Normal state and should not be subject to hilo alarm limit checking. This is primarily intended to be used in bi-directional flow measurements where no flow is considered a normal state and reduces nuisance alarms. This can be used in conjunction with the analog and rate low cutoff feature, where values below a cutoff are replaced with zero.
To configure zero as a normal state
-
In the %DNADataRoot%\RealTime\config\Settings directory, either create or open the RealTime_AbsAlarmingZeroIsNormalState.json file.
-
In the following line, change false to true.
"RealTime" > "ABS_ALARMING_ZERO_IS_NORMAL_STATE": false
-
Save the file.
-
Restart the RealTime service.