Please ensure Javascript is enabled for purposes of website accessibility
Powered by Zoomin Software. For more details please contactZoomin

AVEVA Enterprise SCADA

Abdf1 Row Edit: Poll Table tab

  • Last UpdatedApr 24, 2025
  • 2 minute read

Use the Poll Table tab in the abdf1 Row Edit dialog box to define file types, register ranges, and poll information.

The Poll Table allows for a maximum of 30 different poll ranges to be defined for an Abdf1 remote. Each range is polled for with its own query.

Refer to the table below for field descriptions and instructions on how to configure the editable fields.

Embedded Image (65% Scaling) (LIVE)

Item

Description

Name

This field displays the name of the abdf1 record.

File Type

Select the Allen-Bradley data table file type. Refer to Supported file types for point configurationn.

Freq

Enter the interleave frequency at which the host retrieves this data block from the Remote Terminal Unit (RTU):

1 - The host retrieves this data every poll cycle.

2 - The host retrieves data every 2nd poll cycle. etc....

Integ

Select to scan the data defined by this poll block during an integrity scan.

File#

Enter the data table file number, which indicates where a block of data exists. The field accepts up to three digits.

Slot#

If the polling block is an input or output file, enter the slot number for this polling table.

StartElm

Enter the offset from the beginning of the data table file in element units.

Zero is the first element in a data table file.

# of Elms

Enter the number of records of a certain size that must be uploaded.

Reg Size

Select the size of the register for each configured file type.