Configure the host to send device-based history directly to historical collect
- Last UpdatedApr 24, 2025
- 1 minute read
Follow this procedure when Historical point data is stored in a Remote Terminal Unit (RTU) data logger and sent to the AVEVA Enterprise SCADA host, as opposed to collected on the AVEVA Enterprise SCADA host.
The collect Row Edit dialog box is opened through the collect table listing in the Advanced Database Editor (ADE). For general information on ADE, and further information on the collect table, refer to the Advanced Database Editor (ADE) Administrator documentation and volume 1 of the RealTime Administrator documentation, respectively.
To configure the host to send device-based history directly to historical collect
-
Navigate to the collect Row Edit dialog box for the analog record of interest.

-
Enter or select the name of the analog record field whose data you want to collect.
For the Bristol Standard Asynchronous Protocol (BSAP) Driver with Configurable Gas Load (CGL) for OASyS and the Fisher Remote Operations Controller (ROC)/Fisher Remote Operations Controller (ROC) Plus Driver with Configurable Gas Load (CGL) for OASyS, the field must be one of the following:
-
curval (current value)
-
ddmin (minimum value)
-
ddmax (maximum value)
-
-
In the Collect Type field, select device based history.
The system disables the following fields and checkboxes:
-
Collect Period
-
Number of Periods
-
Deadband
-
Enable Summary
-
Fast Trend Only
-