Re-summarize re-polled data
- Last UpdatedApr 24, 2025
- 1 minute read
Follow this procedure to schedule the running of the RTUDataDump program, which locates all modified hours and re-summarizes the data. The program makes use of the same collect summary function.
To re-summarize re-polled data
-
Create a jsh record.

-
In the Command Type field, select SCRIPT.
-
In the Command field, enter rtudatadump.exe.
-
In the Command Argument field, enter the following arguments as desired:
-
-d <log level>, where <log level> = Fatal, Always, DebugLog, Warning, Info, or Verbose (case sensitive).
Note: If the log level is either misspelled or missing, the level defaults to DebugLog.
-
-b <batch size>, where <batch size> = the number of hours to summarize per one run (default is 10).
For information on the remaining fields, refer to volume 1 of the AVEVA Enterprise SCADA RealTime Administrator documentation.
-