Restrict the display of alarm inhibit icons to points with off-normal alarm inhibits
- Last UpdatedApr 24, 2025
- 1 minute read
Note: For information on overriding default configuration settings, refer to Modify configuration settings.
Default Inhibit Icon Behavior (INTERGRATE_STATE_ALARMINHIBIT value is true)
-
By default, if a state alarm inhibit is active on a point, the Alarm Inhibited icon appears next to the point in easy eXtended Operator Station (ezXOS).
Alternate Inhibit Icon Behavior (INTERGRATE_STATE_ALARMINHIBIT value is false)
-
If the configuration setting for this behavior is set to false, the icon only appears next to points with off-normal alarm inhibits.
To restrict the display of Alarm Inhibit icons to points with off-normal alarm inhibits
-
In the %DNADataRoot%\RealTime\config\Settings directory, either create or open the RealTime_StateAlarmInhibit.json file.
-
Change the value of "INTERGRATE_STATE_ALARMINHIBIT" to false.
{
"RealTime": {
"INTERGRATE_STATE_ALARMINHIBIT": true,
"STATE_ALARM_REDUCTION": false
}
}
-
Save the file.
-
Restart the RealTime service.