AVEVA Enterprise SCADA

Restrict the display of alarm inhibit icons to points with off-normal alarm inhibits

Restrict the display of alarm inhibit icons to points with off-normal alarm inhibits

  • Last UpdatedApr 24, 2025
  • 1 minute read

Note: For information on overriding default configuration settings, refer to Modify configuration settings.

Default Inhibit Icon Behavior (INTERGRATE_STATE_ALARMINHIBIT value is true)

  • By default, if a state alarm inhibit is active on a point, the Alarm Inhibited icon appears next to the point in easy eXtended Operator Station (ezXOS).

Alternate Inhibit Icon Behavior (INTERGRATE_STATE_ALARMINHIBIT value is false)

  • If the configuration setting for this behavior is set to false, the icon only appears next to points with off-normal alarm inhibits.

To restrict the display of Alarm Inhibit icons to points with off-normal alarm inhibits

  1. In the %DNADataRoot%\RealTime\config\Settings directory, either create or open the RealTime_StateAlarmInhibit.json file.

  2. Change the value of "INTERGRATE_STATE_ALARMINHIBIT" to false.

    {

    "RealTime": {

    "INTERGRATE_STATE_ALARMINHIBIT": true,

    "STATE_ALARM_REDUCTION": false

    }

    }

  3. Save the file.

  4. Restart the RealTime service.