Please ensure Javascript is enabled for purposes of website accessibility
Powered by Zoomin Software. For more details please contactZoomin

AVEVA Enterprise SCADA

Analog point configuration

  • Last UpdatedApr 24, 2025
  • 1 minute read

The analog input/output points are configured through the Input/Output tabs in the analog Row Edit dialog box, respectively. For full information on the analog table, refer to volume 1 of the AVEVA Enterprise SCADA RealTime Administrator documentation.

Protocol-Specific Fields

Field

Description

Point Type / Output Type

Select the point type:

  • unsign 16 int

  • signed 16 int

  • unsign 32 int

  • signed 32 int

  • float

  • double

Input Coordinate / Output Coordinate

Type the address where the data is mapped within the Remote Terminal Unit (RTU):

<FileType><FileNumber>:<WordNum>

Where:

FileType is a one-letter code summarized in Supported file types for point configuration.

FileNumber is a decimal number up to three digits in length.

WordNum is a decimal number up to three digits in length.

Example of an Allen-Bradley Analog Coordinate

RTU

Input Coordinate

Output Coordinate

PLC-5

N133:100

N123:104

The Input Coordinate uses the iNteger Type File (N) 133, and reads word 100.