Function puts (fnput) related to alarm bracketing

  • Last UpdatedApr 24, 2025
  • 1 minute read

The table in this section details the Function puts (fnputs) that are specific to alarm bracketing.

Command String

Command Description

Applicable Tables

CLAMP

Re-brackets all the points belonging to an alarm bracket set or an individual point using the default positive and/or negative deviation limits.

See the AVEVA Enterprise SCADA RealTime Controller documentation for more information about re-bracketing operations.

  • almbracket

  • almbracketset

CLAMPUSER <positiveDeviationEnabled> <positiveDeviation> <usePosDevAsPercent><negativeDeviationEnabled> <negativeDeviation> <useNegDevAsPercent>

Re-brackets one individual point belonging to an alarm bracket set using a one-time override of the almbracket record's default positive and/or negative deviation limits configuration.

See Almbracket Row Edit: Alarm Brackets tab for more information about alarm bracketing configuration parameters.

almbracket

SUPERVISOREDIT <positiveDeviationEnabled> <positiveDeviation> <usePosDevAsPercent> <negativeDeviationEnabled> <negativeDeviation> <useNegDevAsPercent>

Configures an almbracket record's default positive and/or negative deviation limits.

almbracket

SUSPEND <suspensionTime>

Temporarily suspends bracketing on the collection of points belonging to an alarm bracket set for the provided amount of time.

almbracketset

UNSUSPEND

Cancels a temporary suspension on a bracketset.

almbracketset