AVEVA Enterprise SCADA

Configure user-defined HiLo alarm limits

  • Last UpdatedApr 24, 2025
  • 1 minute read

You can configure Hi and Lo alarm limits for an analog or a rate point by using the point's Alarm Limits dialog.

Note: In the following procedure, an analog point is used as an example. The procedure is the same for rate points, but slightly different for flowTotalConfig points (as described in the procedure). The Analog Alarm Limits dialog is opened through the Analog Control dialog. For more information on Control dialog boxes, see to the AVEVA Enterprise SCADA HMI Controller documentation.

To configure user-defined HiLo alarm limits

  1. Open the Analog Control dialog.

  2. Select Alarm Limits.

    Note: On the Flow Total Control dialog, select the appropriate Limits button.

    The Analog Alarm Limits dialog appears.

    Embedded Image (65% Scaling) (LIVE)

  3. To enable the User High field in the User Config Alarming section, select Enabled.

  4. To enable the User Low field in the User Config Alarming section, select Enabled.

  5. Depending on your choices in steps 2 and 3, enter a high alarm limit and/or a low alarm limit in the User High and User Low fields, respectively.