Set minimum integrity update poll time

  • Last UpdatedApr 24, 2025
  • 1 minute read

Once a Sub-Remote Status Indicator changes to a Closed state, which indicates sub-remote data is valid, an integrity update poll against the remote is triggered automatically. The integrity update poll processes the current data and updates data quality as soon as possible. To avoid several automated integrity update polls against a remote from occurring too quickly, a delay time should be configured on the remote record.

To configure the minimum integrity update poll delay time for a remote

  1. Navigate to the Main tab in the remote Row Edit dialog box.

    Embedded Image (65% Scaling) (LIVE)

  2. In the Minimum Integrity Poll Delay (sec) field, enter the minimum time between Integrity Update Polls for this remote. If this field is set to zero, a value of 10 seconds will be used.

    Note: This field is only used for automated integrity update polls when there is a Sub-Remote Status Indicator point associated with the remote. It does not limit on-demand integrity update poll requests. Not all protocol drivers support integrity update poll requests.