TrendIndicatorImageSet table details

  • Last UpdatedApr 24, 2025
  • 2 minute read

The TrendindicatorImageSet table is a collection of parameters used against an associated telemetered point value to determine an image that represents a trending indicator displayed by an AVEVA Enterprise SCADA HMI object (such as Flexible Analog Indicator [FAI] rate of change [ROC] trend indication). These parameters include the following:

  • The field whose value determines the image.

  • The thresholds that delimit the value ranges associated with each image.

  • The image to be used for each range.

    Internal Field Name

    Data Type

    Description

    name

    pntname

    The name of the trendIndicatorImageSet record.

    DecreaseThresholds[0-1].Image

    displayname

    The image used to represent the value of the InputField relative to the defined decrease thresholds. Element 0 contains the image for a slowly decreasing value, and element 1 contains the image used for a quickly decreasing value.

    DecreaseThresholds[0-1].Value

    float

    The value that delimits a decreasing range. Element 0 indicates a slowly decreasing range value, and element 1 indicates a quickly decreasing range value.

    description

    pntdescription

    A description of the point, up to 47 characters in length.

    IncreaseThresholds[0-1].Image

    displayname

    The image used to represent the value of the InputField relative to the defined increase thresholds. Element 0 contains the image for a slowly increasing value, and element 1 contains the image used for a quickly increasing value.

    IncreaseThresholds[0-1].Value

    float

    The value that delimits an increasing range. Element 0 indicates a slowly increasing value, and element 1 indicates a quickly increasing value.

    InputField

    pntname

    An input field whose value is used against the TrendIndicatorSet threshold ranges to determine the image representing the current trend indication.

    NormalRangeImage

    displayname

    An image used to indicate that the input value has not exceeded either of the defined thresholds.

    ptnum

    slot

    Slot number in the database.

    tableName

    pntname

    A table for telemetered records to which this set is applicable and limited to.

Related Links