Analog points and rate points with analog input
- Last UpdatedApr 24, 2025
- 1 minute read
Perform this procedure to associate an analog or a rate point (analog input) with a processing deadband.
Note: In the following procedure, an analog point is used as an example. The procedure is similar for configuring a rate point when the Source of Data field on the Main tab in the rate Row Edit dialog box is set to Analog input. The Input tab in the analog Row Edit dialog box is opened through the analog table listing in the Advanced Database Editor (ADE). For general information on ADE, and further information on the analog table, refer to the Advanced Database Editor (ADE) Administrator documentation and RealTime tables, respectively.
To associate an analog or a rate point (analog input) with a processing deadband
-
Navigate to the Input tab in the analog Row Edit dialog box.

-
Select Processing Deadband Enable.
-
In the Processing Deadband field, enter the processing deadband that the system uses to determine whether or not it should process a new value.